background image

18

Figure 27. Typical Oil Piping for Above Ground (Single-Line) Supply

If fuel pump fails to lift oil, check for air

port plug and repeat priming procedure.

leaks and tighten all fuel fittings. Re-
prime fuel pump by injecting fuel oil into
optional (top) return port. Replace return

Top of Tank

8 ft.

Shut-off

Valve

Optional
Fuel
Filter

Alternate

Fuel Line

Entry

Control
Panel

Oil 

Furnace

On-Off-Fan

Switch

Floor Cavity

Oil-Gun
Burner

Floor

Flue Gas

Sampling

  Hole

Drain

End of Oil Supply Line
3" to 5" Above Bottom Drain

Guide

Pipe

Gauge

Vent with cap

2" Duplex
Bushing

2" Fill

3/8" Oil Supply Line

NOTE:

  Additional venting may be 

required if tank is filled rapidly.

4 GPH  100-150 PSI  3450 RPM

3 GPH  150-200 PSI  3450 RPM

VALVE ON DELAY

NO. 2 & LIGHTER FUEL

USE ONLY WITH

INLET

BY-PASS

Exclusively for Beckett

Made by Suntec

INLET

NO. 2 FUEL

A2EA-6520

Beckett 

Nozzle Port

3/16 Flare Fitting

Bypass Solenoid Valve

Cordset

Inlet Port

1/4 NPTF

Bleed & Gauge Port

Pressure Adjustment

Screw

Inlet Port

1/4 NPTF

Return Port - Install 1/6” Bypass Pipe

Plug for 2-pipe System Only.

(Use 5/32” Allen Wrench)

•  The inside of the tank must be clean before fi lling. All 

water, rust, sediment, and debris must be fl ushed out.

•  A fuel or tank gauge (Figure 27) is recommended for 

easy checking of the fuel level. Check the gauge reading 
with a dipstick.

•  Locate the storage tank conveniently near the home. 

If the fuel tank is installed above ground, the tank may 
rest 3 to 4 inches off the ground. Fuel tanks may also 
be buried if properly coated to resist corrosion. The 
vertical dimension from the bottom of the fuel tank to 
the fuel pump must not exceed 10 feet.

•  Keep the tank fi lled, especially in the summer to reduce 

the accumulation of condensation.

One-Line System

The One-Line System is highly recommended where 
vertical lift, from bottom of tank to pump, is less than 8 
feet (Figure 27). A single line hookup has the advantage 
of lower cost and quieter operation.

Two-Line System

If a Two-Line system is used or if oil is taken from the 
bottom of the tank, a fi lter is recommended. A Two-Line 
system should only be used if vertical lift exceeds 8 feet.
1.  Install the oil feed line as outlined in steps 1 - 6 below.
2.  Install the oil pump bypass plug in the bottom return 

port.

3.  Route the return line up through the furnace base to 

the return port of the pump. Route the other end of the 
line to the tank, using 3/8” O.D. copper tubing or 1/4” 
pipe with the ends capped.

4.  Insert the return line through the second opening in the 

duplex bushing. If the bottom of the tank is lower than 
the pump intake, the tube should be inserted three or 
four inches from the tank bottom. If the bottom of the 
tank is higher than the pump intake, the return line 
should extend not more than 8” inside the tank.

Fuel line Hook-Up

1. Use a 3/8” O.D. copper tubing for the fuel line. 

NOTE:

 Cap the end with tape to keep out dirt while the 

line is being routed.

2.  Install duplex bushing for two 3/8” lines in the top fi tting 

of the tank. See Figure 27.

3.  Insert one end of the tubing through the duplex bushing 

until it is three to fi ve inches from the bottom drain. 
Tighten the bushing.

4.  Route the line where it will not incur any damage. Make 

bends gradual and avoid kinks which might restrict oil 
fl ow.

5.  Open the furnace door and connect the oil line to the 

intake port on the pump. Tighten other port plugs on 
the pump. 

NOTE:

 Verify the oil line is airtight! Air leaks 

can cause the pump to lose prime and will create other 
problems such as nozzle failure, odors, rumbling noise, 
and false safety shutdown.

6.  Insert the short length of the copper tube level with the 

bottom of the duplex bushing. Form the tube into an 
inverted “U” to serve as a vent.

Fuel Line Bleeding

To eliminate problems caused by air in the oil line, all 
connections in the oil supply line and all plugs, nuts, 
and fi ttings on the pump must be airtight. 

NOTE:

 This 

includes the nut that covers the pressure adjustment. It 
is important that the hook-up be done carefully and with 
a good fl aring tool.

Prepare the burner for priming by attaching a clear plastic 
hose over the bleed port fi tting and fully opening the pump 
bleed port. Use a suitable container to collect purged oil.

To ensure continuous operation, use a wire to jump 
terminals 

T-T

 (or 

F-F

) on the primary control while burner 

is running.

Содержание M1B 066

Страница 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit...

Страница 2: ...pling 20 STARTUP ADJUSTMENTS 21 Operating Instructions Direct Ignition M1M 22 How to Shut Off Gas Direct Ignition 22 Operating Instructions Oil Gun M5S 22 Operating Instructions Gas Gun M1B 22 How to...

Страница 3: ...the current revision of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CE g n rateur d air chaud doit tre install conform ment aux instructions...

Страница 4: ...equipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used and if applicable a product approved air intake must be used Installation...

Страница 5: ...he overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future servi...

Страница 6: ...e 0 Side Clearance to Furnace Cabinet Provide min 235 sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide...

Страница 7: ...n the floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other o...

Страница 8: ...ellineholesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alco...

Страница 9: ...es X FLOOR OPENING FLOOR CAVITY SUPPLY AIR DUCT Figure 9 Floor Cavity Alternate Attachment Method The standard duct connector is designed for use on ducts 12 in width However if there is insufficient...

Страница 10: ...urn air distributionsystemasshowninFigures14 15 page11 1 Remove furnace outer door s and bottom fuel line knockout 2 Placefurnaceontoductconnectorandcenterwithfloor opening 3 Slideontomountingplate Bo...

Страница 11: ...in the minimum and maximum range of the Roof Jack listed in Table 4 Application Notes FAW FAWT SAW and SAWT Series Roof Jacks with a 5 diameter inner vent pipe may be used with all models of M1 Series...

Страница 12: ...ve along the center line of furnace and floor opening See Figure 19 2 Cut ceiling and roof holes Ceiling 8 3 4 222 mm diameter Roof 9 3 8 238 mm diameter Installing The Roof Jack 1 Apply caulking comp...

Страница 13: ...inent location inside manufactured home until on site installation 4 The four warning tags supplied must be installed as follows To weather cap To fuel line connection point Gas or furnace burner Oil...

Страница 14: ...operly connected as shown in Figure 25 Route all electrical wiring to the left side of the furnace See Figure 24 For installation of A Cabinet furnaces allow sufficient slack in the wiring if an optio...

Страница 15: ...above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails see Figure 25 3 Connect low voltage circuit to the wall thermostat 4 A hole may be made in the furnace cabinet to eas...

Страница 16: ...or property damage This furnace may be installed with left right or bottom gas entry When connecting the gas supply provide clearance between the gas supply line and the entry hole in the furnace casi...

Страница 17: ...t pressure Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure...

Страница 18: ...o Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route the re...

Страница 19: ...P gas Use the following procedure for gas conversion of the burner Atmospheric Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 22 2 Disconnect the gas pipe union and the el...

Страница 20: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Страница 21: ...sonne ne r pond appeler le service des incendies AVERTISSEMENT STARTUP ADJUSTMENTS PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it must...

Страница 22: ...est setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31...

Страница 23: ...mbustion Air CAUTION Combustionairadjustmentmustbemadeonly by a qualified technician Improper air adjust ment may cause unsafe operation explosion and or fire asphyxiation If the input to the furnace...

Страница 24: ...the gas valve 3 Aftera45secondpurge theignitorisenergizedfora30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve...

Страница 25: ...ch must be set in the ON position for the furnace to operate If blower operation is not desired the furnace On Off switch may be set in the OFF position to cut the electrical power to the furnace See...

Страница 26: ...RX1 scale Normal reading should be 40 75 ohms If above or below this rating at room temperature change ignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignito...

Страница 27: ...attheigniterterminals andthere is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Страница 28: ...L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit If flame sense is weak yello...

Страница 29: ...roper furnace operation Excessive ice formation could restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust port...

Страница 30: ...26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3 50...

Страница 31: ...45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46 2 44 4 42...

Страница 32: ...84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 3...

Страница 33: ...is required for M1MA models and M1MB 090 A C Heating Speeds Refer to Table 12 A C Blower Selection in the manual BLACK WHITE WHITE BLACK BLACK GREEN RED GRAY WHITE RED LO BLACK HIGH BLUE MED HI ORANGE...

Страница 34: ...RD TERMINAL BUSHING BUSHING BUSHING BUSHING W C IGNITER FROM C WIRE GRAY BLACK BLACK FROM W WIRE BLUE GAS GUN BURNER GV PSO FSG C IND L 1 HSI HSIG L 2 W PSI FSI CONTROL MODULE IGNITER L2 MOTOR L2 L2 L...

Страница 35: ...35...

Страница 36: ...ATE UNIT MODEL UNIT SERIAL Minimum clearances per Table 1 page 6 YES NO Has the owner s information been reviewed with the home owner YES NO Has the literature package been left near the furnace YES N...

Отзывы: