Priming furnaces equipped with Honeywell
R7184 primary control:

1.  While the ignition is on, press for 1/2 second (or less), 

and release the reset button. The lockout time will be 
extended to 4 minutes.

2. If prime is not established within the 4 minutes, the 

control will lock out. Press the reset button to reset the 
control.

3. Repeat steps 1 & 2 (if needed) until the oil pump is 

fully primed.

Priming furnaces equipped with Beckett 7505 
primary control:

1.  After the burner starts, press and hold the reset button 

until the yellow LED turns on (15 seconds). This indicates 
that the button has been held long enough.

2.  Release the reset button. The yellow LED will turn off 

and the burner will start up again.

3.  At burner start up, click the reset button while the igniter 

is still on. This transitions the control to a dedicated pump 
prime mode, during which the motor, igniter and valve 
are powered for 4 minutes. The yellow LED will be on. 

NOTE:

 If prime is not established during the four minute 

pump prime mode, repeat step 3 until the oil pump is 
fully primed.

4. When oil fl ow is clear and free of air bubbles, close 

air-bleed valve and tighten. 

NOTE:

 Air bleed out time 

will varies depending on length of oil line, number of 
bends, etc.

Fuel Oil Type

 WARNING:

Do not use gasoline, crankcase oil, or any oil 
containing gasline. Failure to keep supply of oil 
clean by various procedures described above 
may cause failure of certain components such 
as the fuel pump gears, check valve, shaft seal, or 
burner nozzle which may result in a burner fi re.

Do not use fuel oil heavier than Grade No. 2. In areas 
where the oil supply is subject to low temperatures, Grade 
No. 1 may be used.

Conversion to Propane (LP) Gas

 CAUTION:

Furnace conversion must be performed by a 
qualifi ed technician. Improper conversion can 
cause unsafe operation, explosion, fi re and/or 
asphyxiation.

This gas fi red heating appliance was shipped from the 
factory for use with natural gas. However, the appliance 

can be converted for use with LP gas. Use the following 
procedure for gas conversion of the burner.

Atmospheric & Direct Ignition Furnaces

1. Follow the instructions “How to Shut Off Gas” (page 

22).

2.  Disconnect the gas pipe union and the electrical wires 

connected to the gas valve.

3.  Remove the gas valve assembly:

a. Remove screw(s) from gas valve bracket. Gas valve 

and spud may be removed. Orifi ce is located at the 
end of the spud (M1M Models)

b. Remove three (3) bolts from U-shaped manifold plate 

and orifi ce assembly (M1B Models).

5.  Replace the main orifi ce with the L.P. gas orifi ce supplied 

in the envelope located by the gas valve. Verify the 
orifi ce size matches the nameplate or Table 10 (page 
31).

6.  For Honeywell gas valves with the regulator converter: 

a. Unscrew the pressure regulator cap and check for 

the letters NAT or LP. See Figure 28, page 20.

b. Invert the cap and tighten until snug.

7.  For Robertshaw gas valves with the regulator converter: 

a. Remove the black cover and unscrew the converter 

located on top of the gas valve. See Figure 29.

b. Invert the converter. For LP, the red ring will be located 

at the bottom and the LP stamping on the converter 
will appear right side up.

c. Screw converter back into the regulator, hand tight 

plus 1/8 turn. Replace the black cover on the converter 
top to protect the threads.

8.  Reassemble the burner assembly into the furnace.
9. Reconnect the gas piping and electrical wires to the 

gas valve.

10. Open the manual shut-off valve and follow the Lighting 

and Operating instructions on page 22.

High Altitude Conversion

High altitude conversion with this furnace depends on 
the installation altitude and the heating value of the gas. 
The installation of this furnace at altitudes above 2,000 
feet must meet the requirements of the National Fuel Gas 
Code or local jurisdiction. In Canada, the requirements for 
high altitude are different and governed by CGA B149.1. 
Please consult your local code authority.

 WARNING:

The reduction of input rating necessary for high 
altitude installation may only be accomplished 
with factory supplied orifi ces. Do not attempt to 
drill out orifi ces in the fi eld. Improperly drilled 
orifi ces may cause fi re, explosion, carbon 
monoxide poisoning, personal injury or death.

Содержание M1B 066

Страница 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit...

Страница 2: ...pling 20 STARTUP ADJUSTMENTS 21 Operating Instructions Direct Ignition M1M 22 How to Shut Off Gas Direct Ignition 22 Operating Instructions Oil Gun M5S 22 Operating Instructions Gas Gun M1B 22 How to...

Страница 3: ...the current revision of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CE g n rateur d air chaud doit tre install conform ment aux instructions...

Страница 4: ...equipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used and if applicable a product approved air intake must be used Installation...

Страница 5: ...he overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future servi...

Страница 6: ...e 0 Side Clearance to Furnace Cabinet Provide min 235 sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide...

Страница 7: ...n the floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other o...

Страница 8: ...ellineholesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alco...

Страница 9: ...es X FLOOR OPENING FLOOR CAVITY SUPPLY AIR DUCT Figure 9 Floor Cavity Alternate Attachment Method The standard duct connector is designed for use on ducts 12 in width However if there is insufficient...

Страница 10: ...urn air distributionsystemasshowninFigures14 15 page11 1 Remove furnace outer door s and bottom fuel line knockout 2 Placefurnaceontoductconnectorandcenterwithfloor opening 3 Slideontomountingplate Bo...

Страница 11: ...in the minimum and maximum range of the Roof Jack listed in Table 4 Application Notes FAW FAWT SAW and SAWT Series Roof Jacks with a 5 diameter inner vent pipe may be used with all models of M1 Series...

Страница 12: ...ve along the center line of furnace and floor opening See Figure 19 2 Cut ceiling and roof holes Ceiling 8 3 4 222 mm diameter Roof 9 3 8 238 mm diameter Installing The Roof Jack 1 Apply caulking comp...

Страница 13: ...inent location inside manufactured home until on site installation 4 The four warning tags supplied must be installed as follows To weather cap To fuel line connection point Gas or furnace burner Oil...

Страница 14: ...operly connected as shown in Figure 25 Route all electrical wiring to the left side of the furnace See Figure 24 For installation of A Cabinet furnaces allow sufficient slack in the wiring if an optio...

Страница 15: ...above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails see Figure 25 3 Connect low voltage circuit to the wall thermostat 4 A hole may be made in the furnace cabinet to eas...

Страница 16: ...or property damage This furnace may be installed with left right or bottom gas entry When connecting the gas supply provide clearance between the gas supply line and the entry hole in the furnace casi...

Страница 17: ...t pressure Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure...

Страница 18: ...o Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route the re...

Страница 19: ...P gas Use the following procedure for gas conversion of the burner Atmospheric Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 22 2 Disconnect the gas pipe union and the el...

Страница 20: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Страница 21: ...sonne ne r pond appeler le service des incendies AVERTISSEMENT STARTUP ADJUSTMENTS PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it must...

Страница 22: ...est setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31...

Страница 23: ...mbustion Air CAUTION Combustionairadjustmentmustbemadeonly by a qualified technician Improper air adjust ment may cause unsafe operation explosion and or fire asphyxiation If the input to the furnace...

Страница 24: ...the gas valve 3 Aftera45secondpurge theignitorisenergizedfora30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve...

Страница 25: ...ch must be set in the ON position for the furnace to operate If blower operation is not desired the furnace On Off switch may be set in the OFF position to cut the electrical power to the furnace See...

Страница 26: ...RX1 scale Normal reading should be 40 75 ohms If above or below this rating at room temperature change ignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignito...

Страница 27: ...attheigniterterminals andthere is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Страница 28: ...L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit If flame sense is weak yello...

Страница 29: ...roper furnace operation Excessive ice formation could restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust port...

Страница 30: ...26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3 50...

Страница 31: ...45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46 2 44 4 42...

Страница 32: ...84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 3...

Страница 33: ...is required for M1MA models and M1MB 090 A C Heating Speeds Refer to Table 12 A C Blower Selection in the manual BLACK WHITE WHITE BLACK BLACK GREEN RED GRAY WHITE RED LO BLACK HIGH BLUE MED HI ORANGE...

Страница 34: ...RD TERMINAL BUSHING BUSHING BUSHING BUSHING W C IGNITER FROM C WIRE GRAY BLACK BLACK FROM W WIRE BLUE GAS GUN BURNER GV PSO FSG C IND L 1 HSI HSIG L 2 W PSI FSI CONTROL MODULE IGNITER L2 MOTOR L2 L2 L...

Страница 35: ...35...

Страница 36: ...ATE UNIT MODEL UNIT SERIAL Minimum clearances per Table 1 page 6 YES NO Has the owner s information been reviewed with the home owner YES NO Has the literature package been left near the furnace YES N...

Отзывы: