Operating Instructions for Direct Ignition 
Furnaces  (M1M Models)

Direct ignition furnaces do not have a pilot. Ignition is 
accomplished by a silicon carbide hot surface ignitor. A 
control module takes care of all timing functions. After 
lighting, the control module uses the ignitor as a fl ame 
sensor, shutting off gas should the fl ame go out. There 
are no external relays or timing devices. 

Do not try to 

light this furnace by hand. The control module is not 
fi eld serviceable.

1.  Set the thermostat to the lowest setting.
2.  Turn off all electric power to the appliance.
3.  Remove the furnace door and turn off the gas valve:

• Honeywell: push in and turn the gas control knob 

clockwise to 

OFF

 (Figure 30)

• Robertshaw: push the gas control lever to the 

OFF 

position (Figure 31). 

Do not force!

4.  Wait ten (10) minutes to clear out any gas. If you smell 

gas, 

STOP!

 and follow the Safety Information on page 

19. If you do not smell gas, proceed to next step 5.

5.  Set the thermostat MODE the 

ON

 position.

6.  Turn the gas valve ON:

•  Honeywell: push in and turn gas control knob counter-

clockwise to 

ON 

(Figure 30).

•  Robertshaw: push the gas control lever to the 

ON 

position 

(Figure 31). 

Do not force!

7.  Replace the furnace door.
8.  Turn on all electric power to the appliance.
9. Change the thermostat mode to 

HEAT

 and the 

temperature selector to a desired temperature level. 
The igniter should light in approximately 75 seconds. 
If the appliance will not operate, see “How To Shut Off 
Gas - Direct Ignition” and call your service technician 
or gas supplier. 

NOTE: 

In the event of any fl ashback or explosion, 

immediately shut off the furnace and call your service 
technician.

How to Shut Off Gas - Direct Ignition

1.  Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance before 

servicing unit.

3.  Set the furnace On-Off Switch to 

OFF

.

•  Honeywell (Figure 30): Turn gas control knob clockwise 

to 

OFF

, Robertshaw (Figure 31): Push the gas control 

lever to 

OFF.

•  For oil, shut off all valves.

4.  Replace the furnace door.

Operating Instructions for Oil Gun 
Furnaces (M5S Models)

If your furnace model number begins with M5S*, the 
furnace is equipped with an ignition device which 
automatically lights the burner.

 

Do not try to light this 

furnace manually

.

1.  Open all valves in the oil line.
2.  Verify the fi re door is closed.
3.  Set the furnace On-Off switch to 

ON

.

4.  Set the thermostat to the desired setting.

NOTE:

 M5 oil gun furnaces may be converted to gas gun 

in the fi eld by using the proper conversion kit listed in the 
Replacement Parts List.

Operating Instructions for Gas Gun 
Furnaces (M1B Models)

If your furnace model number begins with M1B, the furnace 
does not have a pilot. Ignition is accomplished by a silicon 
carbide hot surface ignitor. A control module takes care 
of all lighting and timing functions. There are no external 
relays or timing devices.

 

Do not try to light this furnace 

by hand. The control module is not fi eld serviceable.

1.  Before operation, smell for gas all around the furnace, 

especially near the fl oor because some gases are 
heavier than air and will settle on the fl oor. If you detect 
gas, STOP and follow all the safety instructions.

2.  Set the thermostat to the lowest setting.
3.  Turn off all electric power to the appliance.
4.  Turn off the gas valve:

• Honeywell: push in the gas control knob and turn 

clockwise to 

OFF

 (Figure 30).

•  Robertshaw: push the gas control lever to 

OFF

 (Figure 

31).The lever cannot be placed in the off position unless 
it is pushed in slightly. 

DO NOT FORCE!

Figure 30. Direct Ignition Gas Valve - Honeywell

GAS CONTROL KNOB

Gas Control Lever

Figure 31. Direct Ignition Gas Valve - Robertshaw

Содержание M1B 066

Страница 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit...

Страница 2: ...pling 20 STARTUP ADJUSTMENTS 21 Operating Instructions Direct Ignition M1M 22 How to Shut Off Gas Direct Ignition 22 Operating Instructions Oil Gun M5S 22 Operating Instructions Gas Gun M1B 22 How to...

Страница 3: ...the current revision of the National Fuel Gas Code NFPA54 ANSIZ223 1 ortheNaturalGasandPropane Installation Code CAN CGA B149 1 CE g n rateur d air chaud doit tre install conform ment aux instructions...

Страница 4: ...equipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used and if applicable a product approved air intake must be used Installation...

Страница 5: ...he overall size of the furnace and the installation clearances listed in Table 1 and in Figure 4 page 6 Alcove installations minimum 18 clearance at front of furnace shall be provided for future servi...

Страница 6: ...e 0 Side Clearance to Furnace Cabinet Provide min 235 sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide...

Страница 7: ...n the floor or ceiling registers serving the return air duct system must be at least 235 in2 At least one register should be located where it is not likely to be covered by carpeting boxes and other o...

Страница 8: ...ellineholesmustbecarefullylocated to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 9 For round ducts see Figure 7 1 Measure 10 from the rear wall or alco...

Страница 9: ...es X FLOOR OPENING FLOOR CAVITY SUPPLY AIR DUCT Figure 9 Floor Cavity Alternate Attachment Method The standard duct connector is designed for use on ducts 12 in width However if there is insufficient...

Страница 10: ...urn air distributionsystemasshowninFigures14 15 page11 1 Remove furnace outer door s and bottom fuel line knockout 2 Placefurnaceontoductconnectorandcenterwithfloor opening 3 Slideontomountingplate Bo...

Страница 11: ...in the minimum and maximum range of the Roof Jack listed in Table 4 Application Notes FAW FAWT SAW and SAWT Series Roof Jacks with a 5 diameter inner vent pipe may be used with all models of M1 Series...

Страница 12: ...ve along the center line of furnace and floor opening See Figure 19 2 Cut ceiling and roof holes Ceiling 8 3 4 222 mm diameter Roof 9 3 8 238 mm diameter Installing The Roof Jack 1 Apply caulking comp...

Страница 13: ...inent location inside manufactured home until on site installation 4 The four warning tags supplied must be installed as follows To weather cap To fuel line connection point Gas or furnace burner Oil...

Страница 14: ...operly connected as shown in Figure 25 Route all electrical wiring to the left side of the furnace See Figure 24 For installation of A Cabinet furnaces allow sufficient slack in the wiring if an optio...

Страница 15: ...above the control panel 2 Connectthethermostatwirestothefurnacelowvoltage pigtails see Figure 25 3 Connect low voltage circuit to the wall thermostat 4 A hole may be made in the furnace cabinet to eas...

Страница 16: ...or property damage This furnace may be installed with left right or bottom gas entry When connecting the gas supply provide clearance between the gas supply line and the entry hole in the furnace casi...

Страница 17: ...t pressure Pressure is reduced to 3 1 2 W C by the pressure regulator in the gas valve The maximum inlet pressure for the valve is 7 W C and the minimum inlet pressure is 4 5 W C For L P gas pressure...

Страница 18: ...o Line system should only be used if vertical lift exceeds 8 feet 1 Install the oil feed line as outlined in steps 1 6 below 2 Install the oil pump bypass plug in the bottom return port 3 Route the re...

Страница 19: ...P gas Use the following procedure for gas conversion of the burner Atmospheric Direct Ignition Furnaces 1 Follow the instructions How to Shut Off Gas page 22 2 Disconnect the gas pipe union and the el...

Страница 20: ...nace installation A flue gas sample may be taken from the heat exchanger which is located behind the hole of the top front of blower compartment 1 Turn off all electric power to the appliance 2 Remove...

Страница 21: ...sonne ne r pond appeler le service des incendies AVERTISSEMENT STARTUP ADJUSTMENTS PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE WARNING Before placing the furnace in service it must...

Страница 22: ...est setting 2 Turn off all electric power to the appliance before servicing unit 3 Set the furnace On Off Switch to OFF Honeywell Figure 30 Turn gas control knob clockwise to OFF Robertshaw Figure 31...

Страница 23: ...mbustion Air CAUTION Combustionairadjustmentmustbemadeonly by a qualified technician Improper air adjust ment may cause unsafe operation explosion and or fire asphyxiation If the input to the furnace...

Страница 24: ...the gas valve 3 Aftera45secondpurge theignitorisenergizedfora30 second warm up period After warm up the gas valve opens NOTE The time for ignition is approximately 6 seconds after which the gas valve...

Страница 25: ...ch must be set in the ON position for the furnace to operate If blower operation is not desired the furnace On Off switch may be set in the OFF position to cut the electrical power to the furnace See...

Страница 26: ...RX1 scale Normal reading should be 40 75 ohms If above or below this rating at room temperature change ignitor 3 Check for continuity from ignitor receptacle to burner Control Module is Powered Ignito...

Страница 27: ...attheigniterterminals andthere is no ignition the igniter is likely defective and needs to be replaced 3 If the stops flashing burner turns on but the control locks out again check the cad cell If the...

Страница 28: ...L1 neutral reversed or L1 voltage not present on L1 Flame Status A Yellow LED labeled Flame is provided to indicate flame status When flame is sensed the flame LED is lit If flame sense is weak yello...

Страница 29: ...roper furnace operation Excessive ice formation could restrict the combustion air supply to the burner causing inefficient burner operation If excessive ice has formed on the air inlet or exhaust port...

Страница 30: ...26 43 0 3 x x 1 4 3 M1BC 066 66 53 26 43 0 3 x x 1 2 4 M1BB 086 86 68 18 37 0 3 x x 1 4 3 M1BC 086 86 68 18 37 0 3 x x 1 2 4 M5SB 066 66 56 0 3 50 Gph x Burner Model AF 10 1 4 3 M5SC 066 66 56 0 3 50...

Страница 31: ...45 4 41 8 40 1 38 5 37 0 35 5 34 1 32 7 31 4 30 2 M1M 070 Orifice Size Nat Gas 24 25 26 27 27 28 28 29 29 30 Orifice Size LP 42 42 43 43 43 44 44 45 46 47 Output MBTUH 56 7 52 3 50 2 48 2 46 2 44 4 42...

Страница 32: ...84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 3...

Страница 33: ...is required for M1MA models and M1MB 090 A C Heating Speeds Refer to Table 12 A C Blower Selection in the manual BLACK WHITE WHITE BLACK BLACK GREEN RED GRAY WHITE RED LO BLACK HIGH BLUE MED HI ORANGE...

Страница 34: ...RD TERMINAL BUSHING BUSHING BUSHING BUSHING W C IGNITER FROM C WIRE GRAY BLACK BLACK FROM W WIRE BLUE GAS GUN BURNER GV PSO FSG C IND L 1 HSI HSIG L 2 W PSI FSI CONTROL MODULE IGNITER L2 MOTOR L2 L2 L...

Страница 35: ...35...

Страница 36: ...ATE UNIT MODEL UNIT SERIAL Minimum clearances per Table 1 page 6 YES NO Has the owner s information been reviewed with the home owner YES NO Has the literature package been left near the furnace YES N...

Отзывы: