6 Technical Data
NivuLink Compact - Document revision 02 / 06.08.2020
page 29
6.3 Power supply
Power supply
DC 24 V (−25 % … +30 %)
Max. input current (24 V)
550 mA
Power failure time acc. IEC 61131-2
Depending on external buffering
Total current for clamps (5 V)
700 mA
Isolation
500 V system/supply
Tab. 6-5 Technical data – Power supply
Buffer for system power supply!
The system power supply must be buffered to bridge power outages. As the power de-
mand depends on the respective node configuration, buffering is not implemented internal-
ly. To achieve power outages of 1 ms to 10 ms according to IEC61131-2, determine the
buffering appropriate for your node configuration and structure it as an external circuit.
6.4 Clock
Drift – system clock (25 °C)
20 ppm
Drift - RTC (25 °C)
3 ppm
Buffer time RTC (25 °C)
30 days
Tab. 6-6 Technical data – Clock
6.5 ETHERNET
ETHERNET
2 x RJ-45 (switched or separated mode)
Transmission medium
Twisted Pair S-UTP, 100
Ω, Cat
5,
100 m maximum cable length
Baud rate
10/100 Mbit/s; 10Base-T/100Base-TX
Protocols
DHCP, DNS, SNTP, FTP, FTPS (only ex-
plicit connections), SNMP, HTTP, HTTPS,
SSH, MODBUS (TCP, UDP)
MODBUS input and output
process image, max.
e!RUNTIME
32.000 words
Tab. 6-7 Technical data – ETHERNET
No direct access from fieldbus to the process image of the terminals!
Any data that is required from the local bus process image must be explicitly mapped in the
CODESYS program to the data in the fieldbus process image and vice versa! Direct ac-
cess is not possible!