Instruction Manual
NivuLink Compact
page 40
NivuLink Compact - Document revision 02 / 06.08.2020
8.4 Power Supply Concept
8.4.1 Protection of the Electronics Power Supply
CAUTION
Power electronic components only with appropriate protection measures!
Power the electronic components of the controller only through connectors 1 and 5 using a
2 A slow-blow fuse. Higher currents may damage the electronic components.
Connector
Name
Description
1
24 V
System supply v24 V
2
+
Field supply voltage U
V
3
-
Field supply voltage 0 V
4
Ground
Field supply voltage Ground
5
0 V
System supply voltage 0 V
6
+
Field supply voltage U
V
7
-
Field supply voltage 0 V
8
Ground
Field supply voltage Ground
Fig. 8-2
Protection of electronics power supply