Instruction Manual 

NivuLink Compact 

 

page 14 

NivuLink Compact - Document revision 02 / 06.08.2020 

3.2  Security Measures and Precautions 

To install the unit in your plant and during operation observe the following safety in-
formation: 

 

 

DANGER 

Risk of electric shock 

Prior to installation, repairs or maintenance works: 

 

Always deactivate all power sources used for the unit. 

 

 

 

DANGER 

Risk of fire 

NivuLink Compact is an open system. 

 

Operate NivuLink Compact only in lockable housings, cabinets or in electrical op-
erating areas.  

 

Allow access only to qualified personnel by using a key or appropriate tools. 

 

 

 

WARNING 

Risk of personal injury 

due to disregarding applicable accident prevention regulations. 

 

For installation, commissioning, operation, maintenance and repairs observe the 
accident prevention regulations that apply for your machine/plant such as the 
DGUV Regulation 3 "Electrical Plants and Equipment". 

 

 

 

 

DANGER 

Risk of personal injury and system malfunctions 

due to improper connection. 

 

Observe to lay data lines and supply lines according to standards and make sure 
to use the correct terminal wiring.  

 

Observe the EMC directives that apply for your application. 

 

 

 

CAUTION 

Risk of plant malfunctions 

 

Use devices featuring ETHERNET-/RJ-45 connections only in LANs.  

 

Never connect such devices to telecommunications networks such as analog or 
ISDN telephone systems. 

 

 

 

CAUTION 

Risk of malfunctions 

due to defective or damages devices. 

 

Replace defective or damages devices (e.g. with deformed contacts). 

 

 

 

 

Содержание NivuLink Compact Log

Страница 1: ...ne 49 0 7262 9191 0 Fax 49 0 7262 9191 999 E mail info nivus com DATA TECHNOLOGY Instruction Manual NivuLink Compact Firmware version 11 Document revision 02 06 08 2020 Original Manual German rev 02 a...

Страница 2: ...ankreich Phone 33 0 388 9992 84 info nivus fr www nivus fr NIVUS Ltd United Kingdom Wedgewood Rugby Road Weston under Wetherley Royal Leamington Spa CV33 9BW Warwickshire Phone 44 0 8445 3328 83 nivus...

Страница 3: ...in the European Economic Area EEA this instruction manu al must be translated into the language of the country in which the device is to be used Should the translated text be unclear the original inst...

Страница 4: ...Change History page 4 NivuLink Compact Document revision 02 06 08 2020 Change History Revision Datum Changes Editor 02 06 08 2020 Creation KG 01 Was skipped 00 Was skipped...

Страница 5: ...nty 11 2 5 Disclaimer 12 3 Safety Instructions 13 3 1 Used Symbols and Signal Words 13 3 2 Security Measures and Precautions 14 3 3 Intended Use 16 3 4 User s Responsibilities 16 3 5 Personnel Require...

Страница 6: ...Clamp RCP0 750 4530 31 6 10 Digital Input Clamp RCP0 750 1405 32 7 Mounting 33 7 1 Installation Position 33 7 2 Dimensions 33 7 3 Mounting onto Carrier Rail 34 7 4 Spacing 35 7 5 Mounting Sequence 36...

Страница 7: ...nfiguration via Web Based Management WBM 53 10 1 Basic Instructions 53 10 2 Access Rights 53 10 3 Call Up WBM 54 10 4 WBM Screen Layout 55 10 5 Log In with WBM 56 10 6 Change IP Address of the NivuLin...

Страница 8: ...Instruction Manual NivuLink Compact page 8 NivuLink Compact Document revision 02 06 08 2020 14 Dismantling 64 15 Disposal 65 Index 66 EU Declarations of Conformity 68...

Страница 9: ...ion and connection since it contains relevant information on this product Observe the notes and particularly fol low the warning notes and safety instructions If you should have problems to understand...

Страница 10: ...field Value Input or value to se lect Value to be specified or selected by user Status Status or mode Name of device status or device mode Button Button Button labels in dialogues Key Key labels on ke...

Страница 11: ...t 2 2 Required Documentation and the safety notes and instructions contained therein are observed no functional restrictions are to be expected and perfect operation should be pos sible Please also no...

Страница 12: ...ersons or companies author ised by NIVUS for damages to persons or objects resulting from the use of instruments in technically imperfect condition for damages to persons or objects resulting from the...

Страница 13: ...medium degree of risk Indicates a possible danger with medium risk which may result in a life threatening situa tion or severe bodily injury if it is not avoided CAUTION Warnings in low risk or proper...

Страница 14: ...rding applicable accident prevention regulations For installation commissioning operation maintenance and repairs observe the accident prevention regulations that apply for your machine plant such as...

Страница 15: ...tact area functionality in connection with contamination CAUTION Risk of malfunctions Contact spray may impair contact area functionality in connection with contamination Do not use contact spray CAUT...

Страница 16: ...s of water Operating the units in wet and dusty environments is not allowed unless stated otherwise 3 4 User s Responsibilities Important Note In the EEA European Economic Area national implementation...

Страница 17: ...and the automation environment Personnel authorised by the plant operator Requirements to persons with access to control functions Sufficient knowledge on PLC programming Personnel authorised by the...

Страница 18: ...cable 1 1 1 1 Tab 4 1 Scope of delivery Check additional accessories depending on your order and by using the delivery note 4 2 Receipt Inspection Check the packaging for visible damage immediately a...

Страница 19: ...l packaging Insufficiently franked shipments will not be accepted 5 Product Specification 5 1 Device Versions Art No Name Linkage NLC0 CLOG E0 NivuLink Compact Log Analog and digital signals NLC0 CLOG...

Страница 20: ...oller component cannot be removed 9 Analog input clamps RCP0 750 4530 only for NLC0 CLOG 10 Digital input clamp RCP0 750 1405 only for NLC0 CLOG 11 Bus terminal clamp RCP0 750 6000 12 Power contacts f...

Страница 21: ...identification Connector pin assignment Serial number Approval information Manufacturing Number Fig 5 2 Marking Area for Serial Numbers There are two serial numbers in two rows in the side marking Th...

Страница 22: ...mber The first 4 digits of the serial number correspond with the manufacturing date year and week no of the completed unit e g 1903NLC0 Fig 5 3 NivuLink Compact ID plate In case of enquiries and order...

Страница 23: ...Off Off Off Off No service Yel low Off Off Off Off Level 1 Connection failures likely Connection fail ures likely Green Off Off Off Off Level 2 HSDPA possi ble unstable connection GPRS very slow data...

Страница 24: ...2 1 Modem not connected Flashing red flash code 2 2 Modem initialisation error incompatible firmware version Flashing red flash code 2 3 Modem reset timeout Tab 5 3 LED NET Network status 5 4 3 Syste...

Страница 25: ...onfiguration error Tab 5 5 LED I O Internal data bus status 5 4 5 Module Status Input terminal clamp status LED Status Remarks MS Off No error Flashing red flash sequence Configuration error Tab 5 6 L...

Страница 26: ...r switch Position Switch Mode Function RUN Detent Normal operation e RUNTIME applications running STOP Detent Stop All e RUNTIME applications stopped RESET Momentary Reset warm boot actions 2 7 second...

Страница 27: ...rror AI 4 9 Data contacts 10 AI 2 11 Ground 12 AI 4 13 Ground 14 Power contacts All specified ground potentials relate to the same ground potential and are not specified individually for the single an...

Страница 28: ...3 937 inch Weight 51 226 g Tab 6 2 Technical data Device data analog input clamp Digital Input Clamp RCP0 750 1405 only for Art NLC0 CLOG Width 12 mm 0 472 inch Height 69 mm 2 717 inch Height as of ca...

Страница 29: ...or your node configuration and structure it as an external circuit 6 4 Clock Drift system clock 25 C 20 ppm Drift RTC 25 C 3 ppm Buffer time RTC 25 C 30 days Tab 6 6 Technical data Clock 6 5 ETHERNET...

Страница 30: ...tacts Spring contact self cleaning Tab 6 10 Technical data Power jumper contacts Data contacts Slide contact hard gold plated self cleaning Tab 6 11 Technical Data Data contacts 6 8 Environmental Cond...

Страница 31: ...atus optional Typ conversion period 10 ms Measurement error reference temperature 25 C Measurement error max deviation from full scale end value 0 1 Max temperature error from full scale end value 0 0...

Страница 32: ...2 1 mA Max input current per channel with signal 1 2 4 mA Voltage range for signal 0 DC 3 5 V Voltage range for signal 1 DC 15 30 V Max data width of input data internal 16 Bit System supply voltage...

Страница 33: ...end stop has to be mounted underneath the fieldbus node as an additional safeguard against slipping End stop clamps by WAGO see Chapter 12 2 7 2 Dimensions NLC0 CLOG NLC0 CS70 NLC0 CNF0 1 Depth 100 m...

Страница 34: ...sed then a technical inspection and approval of the rail by WAGO Kontakttechnik GmbH Co KG should take place Carrier rail requirements Carrier rails have different mechanical and electrical properties...

Страница 35: ...on the bottom of the housing must have low impedance contact with the DIN rail wide contact surface is possible Observe for increased vibration and shock loads Install carrier rail with a maximum fast...

Страница 36: ...ontacts On some terminal clamps the groves are locked on the top It is not possi ble to insert terminal clamps with blade contacts on the left into such ter minal clamps from the top right This mechan...

Страница 37: ...he controller on the carrier rail When replacing the controller for an already available controller position the new controller so that the tongue and groove joints to the subsequent clamp are engaged...

Страница 38: ...e NivuLink Compact the following warnings and hints shall be observed right as the warnings and hints found in the according chapters on installation WARNING Danger of electric shock Disconnect the in...

Страница 39: ...sufficient for the maximum current load for all of the input output terminal clamps to be supplied with power Observe for connection The WAGO CAGE CLAMP connection is appropriate for solid stranded an...

Страница 40: ...ic components of the controller only through connectors 1 and 5 using a 2 A slow blow fuse Higher currents may damage the electronic components Connector Name Description 1 24 V System supply voltage...

Страница 41: ...use an additional WAGO Potential Supply Module 750 601 602 610 downstream of the WAGO Power Supply Filter 750 626 8 5 NLC0 CLOG 8 5 1 Analog Inputs 8 5 1 1 Connection Wiring AI 1 AI 2 Ground Ground A...

Страница 42: ...NivuLink Compact page 42 NivuLink Compact Document revision 02 06 08 2020 8 5 1 2 Wiring Examples Fig 8 5 Connecting a 2 wire probe e g pressure probe i Sensor to NLC0 CLOG Fig 8 6 Connecting a 3 wire...

Страница 43: ...h a wide spread with compensating currents flowing or where higher impulse type cur rents e g due to atmospheric discharge may occur Keep data and signal lines away from interfering sources Always lay...

Страница 44: ...uLink Compact Document revision 02 06 08 2020 Fig 8 7 Example WAGO Screen Connection System Fig 8 8 Using the WAGO Screen Connection System 8 5 2 Digital Inputs DI 13 DI 16 Digital inputs with counter...

Страница 45: ...BW4 DBW6 DBW8 DBW10 DBW12 DBW14 Transmission in 0 65535 digits Tab 8 1 NLC0 CS70 preconfigured settings Set up communication to PLC Via ETHERNET use network cable and ETHERNET interface X1 or X2 on Ni...

Страница 46: ...vel Flow velocity Water temperature Air temperature The setting below is preconfigured and cannot be modified IP address NivuFlow 192 168 1 11 Modbus Port 502 Set up communication to NivuFlow Via ETHE...

Страница 47: ...d wastewater hydraulics are preconditions for putting the NivuLink Compact into operation Commissioning of the entire measurement system shall not be carried out before installation has been finished...

Страница 48: ...ller which now has been started Tab 9 1 LED behaviour during boot Should there be no executable program available in the controller or if the operation mode switch is set to STOP this will be indicate...

Страница 49: ...thernet interfaces Host PC The default IP address of the controller is 192 168 1 111 the host PC must be within the same subnet Therefore in the network mask 255 255 255 0 the first three digits of th...

Страница 50: ...system is described be low Procedure 1 Call up prompt a Type cmd into the search box of the task bar b Confirm with Enter The prompt opens 2 Determine IP address of the host PC a Type command ipconfig...

Страница 51: ...apter Settings The network connections are called up 4 Right click to select the network connection The context menu opens 5 Select Properties The connection properties are shown 6 Double click to sel...

Страница 52: ...be lost by shutting down the controller too soon Only restart the controller using the software reboot function in Web Based Man agement WBM This ensures that all memory operations are completed corre...

Страница 53: ...ssioning of the NivuLink Compact by using WBM 10 1 Basic Instructions Should cookies be deactivated in your browser observe the information below You can continue using WBM as long as you move directl...

Страница 54: ...g ETHERNET interface X1 2 Open Internet browser recommended Google Chrome 3 Type https 192 168 1 111 into address line and confirm with Enter The Web Based Management WBM will open up and the connecti...

Страница 55: ...logged in user name 4 When a user is logged in Logout button When no user is logged in Login button 5 Navigation here all entries and sub entries can be selected if required Entry highlighted blue se...

Страница 56: ...Your current user name is shown in the WBM header line Fig 10 2 WBM login mask 10 6 Change IP Address of the NivuLink Compact You can change the pre set IP address of the NivuLink Compact to that of y...

Страница 57: ...the IP Address input field b Use Submit or Enter to confirm A new IP address is assigned to the X1 and X2 ETHERNET interfaces of the control ler 10 7Reboot Function Restart controller using the reboot...

Страница 58: ...ivuLink Compact The USR LED on the NivuLink Compact indicates the status of the connection to the NIVUS WebPortal see Chap 5 4 6 The procedure below describes how to determine the connection status in...

Страница 59: ...verview on the configu ration options and the basic procedures 11 3 1 Edit Process Variable Prerequisites The NIVUS WebPortal is open and you are logged in as administrator Connection between NLC and...

Страница 60: ...Variables The configuration options shown in the Edit Process Variable window depend on the type of process variable s The table below gives an overview on the entry options Representation Function En...

Страница 61: ...USV Combi UPS switching power adapter 24 V DC 5 A AC con verter 230 V AC to 24 V DC NLF0 USV AKKU 12 Maintenance free rechargeable lead gel battery 24 1 2 Ah for combi UPS switching power adapter NLF0...

Страница 62: ...l bluish tinned chromed without slot 210 197 Carrier rail 35 15 1 5 mm steel bluish tinned chromed slotted 210 114 Carrier rail 35 15 1 5 mm steel bluish tinned chromed without slot 210 118 Carrier ra...

Страница 63: ...Fluid and channel hydraulics General regulations for the operators of the measurement facility Ambient conditions NIVUS recommends having the measurement system completely be inspected by a legally as...

Страница 64: ...section fixed component of controller cannot be removed Fig 14 1 Locking the controller Removing the controller 1 Rotate the locking disc using a screwdriver blade until the nose of the locking is no...

Страница 65: ...indicates that the Directive 2012 19 EU on waste electrical and electronic equipment requirements shall be observed on the disposal of the equipment NIVUS GmbH supports and promotes the recycling and...

Страница 66: ...xtensions 61 I Initial start up 47 Installation 38 Intended use 16 IP Address Host PC 49 51 NivuLink Compact 49 L LED Indication Connection status communication hub 25 Fieldbus System 23 Internal data...

Страница 67: ...30 Device data 28 Digital input clamp 32 Environmental conditions 30 ETHERNET 29 Field wiring 30 Mobile radio modem 30 Power jumper contacts 30 Power supply 29 System data 28 Technical Data 28 Termin...

Страница 68: ...t 750 8207 NLC0 CLOG EE NivuLink Compact Log NLC0 CS70 E0 NivuLink Compact S7 NLC0 CS70 EE NivuLink Compact S7 NLC0 CNF0 E0 NivuLink Compact NF NLC0 CNF0 EE NivuLink Compact NF Tab 15 1 Assignment Niv...

Страница 69: ......

Страница 70: ......

Страница 71: ......

Страница 72: ......

Страница 73: ......

Отзывы: