1.4 - Electrical characteristics
• All work relating to installation, commissioning and maintenance must be carried out by experienced, qualified
personnel.
1.4.1 - General characteristics
Characteristics
Level
Power supply voltage
3-phase mains supply: 400V -10% to 480V +6%
Phase voltage imbalance
< 3%
Input frequency
2% around te rated frequency (50 or 60 Hz)
Maximum number of power-ups per hour (power)
• 20
Output frequency range
0 to 200 Hz
Mains short-circuit capability at the point of connection
See section 4.4.3
ROHS conformance
Conforming to standard 2002-95-EC
1.4.2 - Electrical characteristics at +40°C
I
co
: Continuous output current
P
out
: Output power
I
max
(60s)
: Maximum output current*
Heavy duty
: For high overload constant torque machines (presses, grinders, hoists, etc) and all applications where significant inertia
has to be accelerated quickly (centrifuges, translation of travelling cranes, etc).
Normal duty
: For low overload constant torque or centrifugal torque machines (fans, compressors, etc).
*: Current available for 60 seconds every 600 seconds.
The output currents I
co
in the table below are given for:
- A 4 kHz switching frequency,
- An ambient temperature of +40°C,
- An altitude of 1000m maximum.
POWERDRIVE FX
Heavy duty
Normal duty
Size
Rating
P
out
kW
I
co
A
I
max
(60s)
A
P
out
kW
I
co
A
I
max
(60s)
A
2
33T
22
45
68
30
59
64
40T
30
59
89
37
73
79
50T
37
73
105
45
86
95
3
60T
45
92
135
55
110
119
75T
55
110
165
75
145
157
100T
75
145
200
90
175
189
1.4.3 - Derating according to the temperature and switching frequency
POWERDRIVE FX
rating
Duty
I
co
(A)
4kHz
5kHz
6kHz
33T
Heavy
45
43
41
Normal
59
56
53
40T
Heavy
59
55
50
Normal
73
68
62
50T
Heavy
73
68
63
Normal
86
80
74
60T
Heavy
92
88
84
Normal
110
106
100
75T
Heavy
110
100
88
Normal
145
132
116
100T
Heavy
145
131
113
Normal
175
158
137
The I
co
output currents are given at an ambient temperature of +40°C. For a temperature above +40°C, derate the current by 1.5%
for every additional degree up to a maximum temperature of +50°C.
Содержание POWERDRIVE FX 100T
Страница 1: ...POWERDRIVE FX Installation guide 4 quadrant Variable speed drive Part number 4729 en 2017 08 c...
Страница 9: ...9 GENERAL INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c Notes...
Страница 15: ...15 MECHANICAL INSTALLATION POWERDRIVE FX Installation guide 4729 en 2017 08 c Notes...
Страница 37: ...37 UL LISTING INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c NOTES...
Страница 38: ...38 UL LISTING INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c NOTES...
Страница 39: ......