CONNECTIONS
POWERDRIVE FX Installation guide
4729 en - 2017.08 / c
3.1.3 - Cables and fuses
• It is the responsibilityof the user to connect and provide protection for the POWERDRIVE FX in accordance with the
current legislation and regulations in the country of use. This is particularly important as regards the size of the
cables, the type and rating of fuses, the earth or ground connection, powering down, acknowledging trips, isolation and
protection against overcurrents.
• This table is given for information only, and must under no circumstances be used in place of the current standards.
I
co
: Continuous output current
I
L
M
: Maximum continuous line current permitted in motor mode (power drawn by the motor)
I
L
G
: Maximum continuous line current permitted in regenerative mode (power transmitted to the mains supply)
POWERDRIVE FX
Mains supply
Motor (1)
400V - 50Hz
460/480V - 60Hz
I
co
(A)
Cable
cross-
sections
(2)
(mm
2
)
Rating /
duty
I
L
M
(A)
I
L
G
(A)
Fuses
Cable
cross-
sections
(2)
(mm
2
)
I
L
M
(A)
I
L
G
(A)
Fuses
Cable
cross-
sections
(2)
(mm
2
)
Gg
type
aR
type
Gg
type
aR
type
Class
J
33T
Heavy
42
34
50
80
3x10 + 10 37
30
50
80
60 3x10 + 10
45
3x10 + 10
Normal
57
45
63
100
3x16 + 16 50
39
63
100
80
3x16 + 16
59
3x16 + 16
40T
Heavy
57
45
63
100
3x16 + 16 50
39
63
100
80
3x16 + 16
59
3x16 + 16
Normal
68
55
80
125 3x25 + 15 59
48
80
125
100
3x25 + 16
73
3x25 + 16
50T
Heavy
68
55
80
125 3x25 + 16 59
48
80
125
100
3x25 + 16
73
3x25 + 16
Normal
83
66
100
160 3x25 + 16
72
57
100
160
125 3x25 + 16
86
3x25 + 16
60T
Heavy
83
66
100
160 3x25 + 16
72
57
100
160
125 3x35 + 16
92
3x35 + 16
Normal
100
80
125
200
3x50 + 25
87
70
125
200
150 3x35 + 16
110
3x50 + 25
75T
Heavy
100
80
125
200
3x50 + 25
87
70
125
200
150 3x35 + 16
110
3x50 + 25
Normal
135
108
160
250 3x70 + 35
117
94
160
250
200
3x70 + 35
145
3x70 + 35
100T
Heavy
135
108
160
250 3x70 + 35
117
94
160
250
200
3x70 + 35
145
3x70 + 35
Normal
162
130
200
350 3x95 + 50
141
113
200
350
225 3x70 + 35
175
3x95 + 50
(1)
The value of the rated current and the motor cable cross-sections are given for information only. As a reminder, the motor rated
current permitted by the drive varies according to the switching frequency and the temperature.
(2)
The recommended cross-sections have been determined for single-conductor copper cable with a maximum length of 10 m.
For longer cables, take line drops due to the length into account.
Note:
• The cable cross-sections are defined according to the following model:
E.g. for a 100T drive in normal duty, a cable cross-section of (3 x 95 + 50) is given, i.e. 1 bundle consisting of 3 phase conductors
(cross-section 95) and 1 earth conductor (cross-section 50).
• The I
co
output currents are given at an ambient temperature of 40°C. For a temperature above 40°C, derate the current by 1.5%
for every additional degree up to a maximum temperature of 50°C.
Содержание POWERDRIVE FX 100T
Страница 1: ...POWERDRIVE FX Installation guide 4 quadrant Variable speed drive Part number 4729 en 2017 08 c...
Страница 9: ...9 GENERAL INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c Notes...
Страница 15: ...15 MECHANICAL INSTALLATION POWERDRIVE FX Installation guide 4729 en 2017 08 c Notes...
Страница 37: ...37 UL LISTING INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c NOTES...
Страница 38: ...38 UL LISTING INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c NOTES...
Страница 39: ......