CONNECTIONS

POWERDRIVE FX Installation guide

4729 en - 2017.08 / c

3.1.3 - Cables and fuses

• It is the responsibilityof the user to connect and provide protection for the POWERDRIVE FX in accordance with the 

current legislation and regulations in the country of use. This is particularly important as regards the size of the 

cables, the type and rating of fuses, the earth or ground connection, powering down, acknowledging trips, isolation and 

protection against overcurrents.

• This table is given for information only, and must under no circumstances be used in place of the current standards.

I

co

: Continuous output current

I

L

M

: Maximum continuous line current permitted in motor mode (power drawn by the motor)

I

L

G

: Maximum continuous line current permitted in regenerative mode (power transmitted to the mains supply)

POWERDRIVE FX

Mains supply

Motor (1)

400V - 50Hz

460/480V - 60Hz

I

co

(A)

Cable 

cross-

sections 

(2)

(mm

2

)

Rating /

duty

I

L

M

(A)

I

L

G

(A)

Fuses

Cable 

cross-

sections 

(2)

(mm

2

)

I

L

M

(A)

I

L

G

(A)

Fuses

Cable 

cross-

sections 

(2)

(mm

2

)

Gg

type

aR

type

Gg 

type

aR 

type

Class 

J

33T

Heavy

42

34

50

80

3x10 + 10 37

30

50

80

60 3x10 + 10

45

3x10 + 10

Normal

57

45

63

100

3x16 + 16 50

39

63

100

80

3x16 + 16

59

3x16 + 16

40T

Heavy

57

45

63

100

3x16 + 16 50

39

63

100

80

3x16 + 16

59

3x16 + 16

Normal

68

55

80

125 3x25 + 15 59

48

80

125

100

3x25 + 16

73

3x25 + 16

50T

Heavy

68

55

80

125 3x25 + 16 59

48

80

125

100

3x25 + 16

73

3x25 + 16

Normal

83

66

100

160 3x25 + 16

72

57

100

160

125 3x25 + 16

86

3x25 + 16

60T

Heavy

83

66

100

160 3x25 + 16

72

57

100

160

125 3x35 + 16

92

3x35 + 16

Normal

100

80

125

200

3x50 + 25

87

70

125

200

150 3x35 + 16

110

3x50 + 25

75T

Heavy

100

80

125

200

3x50 + 25

87

70

125

200

150 3x35 + 16

110

3x50 + 25

Normal

135

108

160

250 3x70 + 35

117

94

160

250

200

3x70 + 35

145

3x70 + 35

100T

Heavy

135

108

160

250 3x70 + 35

117

94

160

250

200

3x70 + 35

145

3x70 + 35

Normal

162

130

200

350 3x95 + 50

141

113

200

350

225 3x70 + 35

175

3x95 + 50

(1)

 The value of the rated current and the motor cable cross-sections are given for information only. As a reminder, the motor rated 

current permitted by the drive varies according to the switching frequency and the temperature.

(2)

 The recommended cross-sections have been determined for single-conductor copper cable with a maximum length of 10 m. 

For longer cables, take line drops due to the length into account.

Note:

• The cable cross-sections are defined according to the following model:

E.g. for a 100T drive in normal duty, a cable cross-section of (3 x 95 + 50) is given, i.e. 1 bundle consisting of 3 phase conductors 

(cross-section 95) and 1 earth conductor (cross-section 50).

• The I

co

 output currents are given at an ambient temperature of 40°C. For a temperature above 40°C, derate the current by 1.5% 

for every additional degree up to a maximum temperature of 50°C.

Содержание POWERDRIVE FX 100T

Страница 1: ...POWERDRIVE FX Installation guide 4 quadrant Variable speed drive Part number 4729 en 2017 08 c...

Страница 2: ...d to be able to supply a motor and the driven machine above its rated speed If the motor or the machine are not mechanically designed to withstand such speeds the user may be exposed to serious danger...

Страница 3: ...components during transportation and handling Avoid touching electronic components and contact parts The variable speed drives contain parts which are sensitive to electrostatic stresses and may be e...

Страница 4: ...c Axial output Helical gears Motors Gearboxes POWERDRIVE FX RFI filter Encoder or resolver input Additional I O Datalogger Communication options Options HPM motor Motor options MDX KEYPAD MDX SOFT par...

Страница 5: ...1 STO 2 inputs Safe Torque Off function 22 3 3 1 3 phaseAC power supply in accordance with safety standard IEC EN62061 2005 and EN ISO 13849 1 2006 Single channel locking SIL1 PLb 22 3 3 2 3 phaseAC p...

Страница 6: ...back options 29 5 2 5 I O options 29 5 3 RFI filters 30 5 3 1 General 30 5 3 2 Weight and dimensions 30 6 TRIPS DIAGNOSTICS 31 6 1 Drive statut 31 6 2 Alarms 32 6 3 Trips 32 7 MAINTENANCE 35 7 1 Servi...

Страница 7: ...ck POWERDRIVE FX drives are designed for installation in a cabinet or an enclosure to ensure protection from conducting dust and condensation Prevent access by unauthorised personnel Diagram Micro con...

Страница 8: ...fuges translation of travelling cranes etc Normal duty For low overload constant torque or centrifugal torque machines fans compressors etc Current available for 60 seconds every 600 seconds The outpu...

Страница 9: ...9 GENERAL INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c Notes...

Страница 10: ...In atmospheres where condensation may form install a heating system to be switched off when the drive is operating It is advisable to control the heating system automatically The casing of the POWERD...

Страница 11: ...750 692 766 782 788 45 284 78 5 53 5 32 5 49 5 37 4 Lifting rings Fixed with 4 M8 screws Terminal block cover Terminal block cover Front view Side view Dimensions in mm With MDX I O M2M option add 25...

Страница 12: ...with its fixing feed mounted ready for surface mounting For through panel mounting remove the feet and follow the instructions below 2 2 2 1 Ratings 33T to 50T 530 200 18 495 553 486 140 15 40 231 fo...

Страница 13: ...5 78 5 49 5 700 6 for M8 crimp cap nuts Solid surface Back of the cabinet Lifting rings Terminal block cover Terminal block cover Drill hole diagram Side view seal seal 53 5 Dimensions in mm With MDX...

Страница 14: ...ow rate and noise levels Losses Losses W POWERDRIVE FX 33T 40T 50T 60T 75T 100T Total 800 980 1150 1450 1850 2200 Inside the cabinet through panel mounting 90 100 110 140 170 200 Maximum losses for no...

Страница 15: ...15 MECHANICAL INSTALLATION POWERDRIVE FX Installation guide 4729 en 2017 08 c Notes...

Страница 16: ...short circuits The drive stop function does not protect against high voltages on the terminal blocks Check that the voltage and current of the drive the motor and the mains supply are compatible Afte...

Страница 17: ...U V W PE Screw bolt M8 Tightening torque 12 Nm Screw bolt M8 Tightening torque 12 Nm QS Mains supply Optional RFI filter Optional sensor 3 phase motor asynchronous or synchronous MDX ENCODER and or Fi...

Страница 18: ...5 3x25 15 59 48 80 125 100 3x25 16 73 3x25 16 50T Heavy 68 55 80 125 3x25 16 59 48 80 125 100 3x25 16 73 3x25 16 Normal 83 66 100 160 3x25 16 72 57 100 160 125 3x25 16 86 3x25 16 60T Heavy 83 66 100 1...

Страница 19: ...l blocks 3 2 2 1 Characteristics of the PX1 terminal block 1 10V 10 V internal analog source Accuracy 2 Maximum output current 10 mA 2 AI1 Differential analog input 1 3 AI1 Differential analog input 1...

Страница 20: ...is used to maintain the control power supply in the event of mains loss 2 DO1 Digital output Factory setting Zero speed Characteristics Open collector Absolute maximum voltage 30 V 0 V Overload curre...

Страница 21: ...tings The STO 1 and STO 2 inputs must be closed before giving a run command By default the motor sensor detection is disabled If the motor thermal sensor needs to be connected to DI1 CTP set Mtr 06 05...

Страница 22: ...iagrams described in the following paragraphs must be implemented The STO 1 STO 2 inputs are safety components which must be incorporated in the complete system dedicated to machine safety As for any...

Страница 23: ...of R F signals on the power supply cable conducted emissions By direct radiation near to the mains supply power cable or the drive motor cable radiated emissions These phenomena are of direct interest...

Страница 24: ...its impedance is as low as possible so as to distribute the fault currents and high frequency currents without them passing through electronic equipment Metal grounds must be mechanically connected to...

Страница 25: ...EN 61000 3 Emission Standard Categories Size 2 Size 3 Size 2 or 3 with external filter EN 61800 3 C1 To be defined C2 Cable length 10 m Frequency 5 kHz Cable length 10 m Frequency 5 kHz Cable length...

Страница 26: ...e particular applications As soon as it is swithched on the MDX KEYPAD is set to read mode The buttons are used to scroll through the all parameters required for supervision and diagnostics Motor curr...

Страница 27: ...ters can be set using the Parameter setting Parameter setting via the keypad menu Control via the keypad is disabled in factory set configuration Trip history Gives a quick overview of the drive s las...

Страница 28: ...nal modules Several options can be combined Fieldbus options see section 5 2 3 Speed feedback options see section 5 2 4 I O options see section 5 2 5 5 2 3 Fieldbus options Depending on the configurat...

Страница 29: ...umentations 5 2 5 Additional I O options Two options are available to increase the number of inputs outputs of the Powerdrive FX MDX I O Lite MDX I O M2M Functions MDX I O Lite MDX I O M2M Analog inpu...

Страница 30: ...3359 180 28 197 6 34 CAUTION The specific design of these filters makes it possible to use them in the context of installations with a neutral IT point connection The installer must however check that...

Страница 31: ...2 not connected or 06 15 Drive output set to Inhibit Depending on the control logic selected in 06 04 Ctr 06 the motor can start as soon as the drive is enabled OP 1 Drive enabled motor on load 2 Driv...

Страница 32: ...cel the trip If the Run FWD or Run reverse terminal is closed at the time of resetting the motor may or may not start immediately depending on the setting of Ctr 06 06 04 No Reason for trip Possible c...

Страница 33: ...current reference on analog input AI3 30 Loss of communication on the P2 connector serial link Check the cable connections Check the parameter 11 63 is compatible with the timing of requests from the...

Страница 34: ...verheating of phase W IGBTs 60 A problem is detected during the control board and interface test Refer to parameters 17 05 17 08 and 17 09 in the diagnostics menu in commissioning manual ref 4617 63 T...

Страница 35: ...ing maintenance work on the drive There are very few maintenance and repair operations to be performed by the user on POWERDRIVE FX drives Regular servicing operations are described below 7 1 Servicin...

Страница 36: ...id state overload protection for the motor load The drive provides overspeed protection However it does not provide the level of protection afforded by an independent high integrity overspeed protecti...

Страница 37: ...37 UL LISTING INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c NOTES...

Страница 38: ...38 UL LISTING INFORMATION POWERDRIVE FX Installation guide 4729 en 2017 08 c NOTES...

Страница 39: ......

Страница 40: ...Moteurs Leroy Somer Headquarter Boulevard Marcellin Leroy CS 10015 16915 ANGOUL ME Cedex 9 Limited company with capital of 65 800 512 RCS Angoul me 338 567 258 www leroy somer com IMP297NO582...

Отзывы: