Electrical installation
EVC 13
17
The outdoor sensor signal regulates the control unit
so that the correct boiler/flow temperature is obtained.
The relation between the outdoor temperature and
boiler/flow temperature can be set with the help of
“Offset heating curve” and “Heating curve selection”
knobs.
The outdoor sensor is normally positioned on the
north or north-west wall, protected against mechanical
damage. The sensor should measure the correct out-
door temperature and thus not be affected by e.g. the
morning sun. The electrical connection is made on the
relay card's (29) terminal block (14).
Max. permitted cable length:
Cu-cable
Ø 0.6 mm
20 m
Cu-cable
1.0 mm
2
80 m
Boiler/Flow sensor (18), see the section “Component
positions”, reads the flow temperature and sends a
signal to the heating control system, which in turn cor-
rects the flow temperature with the help of the immer-
sion heater.
29
15
12
11
10
9
8
7
6
5
4
3
2
1
14
Boiler/Flow sensor
Outside sensor
The temperature limiter (6) disconnects the power
supply between 90 - 100 °C and can be manually re-
set by pressing the reset button, see the section
“Causes and dealing with malfunctions” - “Resetting
the temperature limiter”.
In normal mode the boiler's flow temperature is limited
by the potentiometer “Temperature limitation”, see the
figure in the section “Electrical installation” - “Output
control immersion heater”. The normal setting should
be approximately 5 °C above the design flow tempera-
ture. In addition to the “Temperature limitation” setting
there is also a “Max thermostat”, whose task is also to
safeguard the limitation of the flow temperature. The
normal setting should be approximately 10 °C above
the design flow temperature. With operations in the R-
position, the flow temperature can be adjusted with
the help of the max thermostat.
Max thermostat/Temperature limitation
Temperature limiter
GRUND
FO
S
Type U
P
S
25 - 60
1
3
0 P/N:5
952644
7
2
3
0-
50Hz
DK
PC:020
2NIB
2,5
u
F
IP 44
TF 110
Cl
ass
H
M
a
x 10
ba
r
1/1(A)
P1(W)
020 45
0
3
0 65
040 90
Effekt-
be
g
rän
s
nin
g
kW
Temperatur
be
g
rän
s
nin
g
50°C
20
8
0
60
40
70
3
0
9
7
11
1
3
5
5
3
5
3
0
10
25
20
15
S
äkrin
gs
-
s
torlek (A)
Max thermostat
Temperature
limitation
Temperature
limiter
Temperature sensor data
-30
53.44
4.60
-20
29.20
4.31
-10
16.62
3.90
-40 102.35
4.78
Temperature (°C)
Resistance (k
)
Voltage (V)
-35 73.51
4.70
-25
39.29
4.47
-15
21.93
4.12
-5
12.71
3.65
0
9.81
3.38
5
7.62
3.09
10
5.97
2.80
15
4.71
2.50
20
3.75
2.22
25
3.00
1.95
30
2.42
1.70
35
1.96
1.47
40
1.60
1.27
45
1.31
1.09
60
0.746
0.70
50
1.08
0.94
70
0.525
0,51