Pipe installation

EVC 13

13

The boiler has the circulation pump placed on the re-
turn pipe. The pump capacity setting is made with the
help of the diagram.

Should a pump find it difficult to start, (for example,
after a long period of being shut off) it can be helped
by temporarily setting the capacity selector to the
highest position to give the maximum starting torque.
When the pump starts, the selector is reset to the pre-
vious setting. When, despite this, the pump does not
start, see the section “Causes and dealing with mal-
functions” - “Helping the circulation pump to start”.
The flow should not exceed 1700 l/h in order to pre-
vent cavitation problems in the pipes.

Pipe installation must be carried out in accordance
with current norms and directives. The boiler is
equipped with R 20 male connections. The shut off
valves should be fitted outside of EVC 13 to facilitate
future service.

Pump and pressure drop

diagrams

EVC 13 is equipped with a tapping valve (51) on the
boiler with an R15 ( 

1

/

2

" ) hose coupling. The cap on

the valve should be dismantled and the hose coupling
screwed on when draining the boiler The tapping
valve is opened. The safety valve (52) is then opened
to provide an air supply. The tapping valve for the radi-
ator system should be located in a suitable position.

Circulation pump

Tapping valve

Filling valve

The waste water pipe should be routed according to
applicable regulations. The waste water pipe from the
safety valve should be routed to a floor drain and de-
signed so that hot water can not splash when the
valve needs to be checked or the boiler vented. The
outlet of the waste water pipe should be visible. When
installing the NIBE COMPACT water heater the elec-
tric boiler's waste water pipe can be routed straight
down through the hot water heater's top plate.

NOTE!

The pipe system should be flushed out

so that contamination can not damage

the equipment.

Waste water pipe

Connections

3

2

1

0

500

1000

0

1500

2000

4

l/h

P

5

6

Tillgänglig pumpkapacitet
(pannans interntryckfall fråndraget)

kPa

60

50

40

30

20

10

0

mvp

Flöde

l/s

0,5

0,4

0,3

0,2

0,1

0

Max flöde: 1700 l/h

Filling connection (79), 15 mm copper tube, is con-
nected to the system’s freshwater supply. When filling
the heating system, the filling valve (49) must be
opened and the system is then filled with water. Note
when the pressure rises on the pressure gauge. When
the pointer reaches 2.5 bar, the safety valve (52)
opens and starts to release air mixed water. Stop fill-
ing. Turn the safety valve until the boiler pressure
reaches the normal working range (0.5 - 1.5 bar).

The electric boiler should be transported and stored in
the dry. EVC 13 is designed to be positioned on top of
an electric water heater type NIBE COMPACT. Make
sure that the anode in the hot water heater is accessi-
ble.

NOTE!

EVC 13 must be installed horizontally, at least

50 cm from the floor. There must be an air gap of at
least 10 mm under the boiler's base plate so that elec-
tric components receive sufficient ventilation air.

A space of approximately 30 cm above and approxi-
mately 60 cm in front of the boiler must be left for in-
stallation and accessibility when performing service
work.

Transport and installation

Max. flow: 1700 Vh

Flow

Available pump capacity
(Boiler's internal pressure drop deducted)

Содержание EVC 13

Страница 1: ...LEK 2 1 bar 3 0 4 20 100 40 80 60 C 0 120 R MOS GB 0527 1 511291 EVC 13 INSTALLATION AND MAINTENANCE INSTRUCTIONS EVC 13...

Страница 2: ...LEK LEK LEK LEK 1 2...

Страница 3: ...aste water pipe 13 Filling valve 13 Tapping valve 13 Circulation pump 13 Pump and pressure drop diagrams 13 Expansion vessel 14 Max radiator volume 14 Pressure controlled bypass valve 14 Draining the...

Страница 4: ...ol of an electric water heater which can be pow ered directly from the boiler The controls are collected and well arranged on the front panel EVC 13 is a swedish made high quality electric boiler of f...

Страница 5: ...ure sensor is supplied The output is connected and disconnected with the help of two contactors and two relays EVC 13 has an integrated circulation pump expansion vessel safety valve tapping valve loa...

Страница 6: ...13 Clock Heating curve selection Offset heating curve Night change Fuse Selector D a y 15 12 24 21 6 18 R 3 9 15 ON OFF 2 1 bar 3 0 4 20 100 40 80 60 C 0 120 Boiler temperature Switch Boiler pressure...

Страница 7: ...ble or breakage Clock The clock is used to manually set the times for enabling and disabling the selected Night change also see under Selector Fuse Fuse 2 5 A for control and the circulation pump Sele...

Страница 8: ...settings use the basic da ta from the map opposite If the required room tempera ture is not obtained readjustment may be necessary NOTE Wait one day between settings so that the tem peratures have ti...

Страница 9: ...room temperature The Night change knob is used when you would like to lower or increase the room temperature during spe cific periods of the day In the home position this knob should be set to 0 A ch...

Страница 10: ...e these two values meet 30 40 50 60 80 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30 15 14 13 11 10 9 8 7 6 5 4 3 2 1 V RMEKURVA 5 5 F RSKJUTNING V RMEKURVA 70 16 17 18 19 12 30 40 50 60 8...

Страница 11: ...r The selector switches between Permanent day Permanent night and Auto mode See the section Front panel Setting the time On Off indication relay status 15 minute key Manual mode Weekday Monday Sunday...

Страница 12: ...vessel s ini tial pressure normally 0 5 1 5 bar When the pres sure is too low there is a risk of not receiving suffi cient heat in all of the radi ators When the pressure is too high the safety valve...

Страница 13: ...e equipped with a Standby mode position 3 on the operating mode switch This mode can be used should the ordinary control system stop working In this mode the max thermostat regulates the boiler flow t...

Страница 14: ...enting screw Start EVC 13 and check whether the circulation pump runs It is usually easier to start the circulation pump with EVC 13 running switch 8 set to 2 If helping the circulation pump to start...

Страница 15: ...the valve needs to be checked or the boiler vented The outlet of the waste water pipe should be visible When installing the NIBE COMPACT water heater the elec tric boiler s waste water pipe can be rou...

Страница 16: ...expansion vessel the distance between the highest radiator and the expansion vessel must not be less than 2 5 m The max permitted radiator volume is 150 litres at an initial pressure of 0 5 bar WARNI...

Страница 17: ...d for centralised load control and has equipment for tariff control of the electric water heater as an extra option Cables enter at the rear or top of the boiler see the section Component positions an...

Страница 18: ...block 14 Protective low voltage Output Step size Load per phase A kW kW L1 L2 L3 4 2 2 5 8 5 8 5 8 6 6 8 7 8 7 8 7 8 6 2 13 7 13 7 8 7 11 6 3 2 18 0 18 0 13 0 Effekt begr nsning kW Temperatur begr nsn...

Страница 19: ...e temperature limiter In normal mode the boiler s flow temperature is limited by the potentiometer Temperature limitation see the figure in the section Electrical installation Output control immersion...

Страница 20: ...d using their respec tive venting screws NOTE The safety valve must be operated very care fully as it opens quickly Filling Venting Readjustment 2 1 bar 3 0 4 The filling connection 79 15 mm copper tu...

Страница 21: ...ing Rumsgivare Utegivare Str mk nnare 12 11 10 9 8 7 6 5 4 3 2 1 14 N Ext 26 Str mst llarl ge D A N 21 Brun Electrical circuit diagram Standard design NOTE Terminal 26 is live even when the switch is...

Страница 22: ...76 85 75 31 20 27 26 77 78 43 9 1 8 13 67 10 42 6 40 22 103 GRUNDFOS Type UPS 25 60 130 P N 59526447 230 50Hz DK PC 020 2NIB 2 5uF IP 44 TF 110 Class H Max 10bar 1 1 A P1 W 020 45 030 65 040 90 86 71...

Страница 23: ...r powering the external water heater 27 Set of fuses accessory 29 Relay card 31 Contactor accessory 34 Microprocessor card 35 Capacity switch circulation pump 40 Temperature gauge boiler water 42 Pres...

Страница 24: ...e for inspection and service EVC 13 260 615 600 40 60 215 160 27 27 10 ca 300 Min 500 Golv Fritt utrymme f r luftspalt ca 600 Matning elpanna Skyddsklensp nning Tariffstyrning vvb Compression ring Tar...

Страница 25: ...osition when tariff con trol is not used Fuse and tariff kits for the power supply of an external electrical hot water heater Room sensor 9 20 13 31 19 8 N L1 L2 L3 N N L1 L2 L3 EXT 27 26 Matning VVB...

Страница 26: ...itres Width 600 mm Weight 36 kg Supply voltage 400 3 conductor N Rated output circulation pump 113 W static pressure height 6 m Max permitted pressure 3 0 bar 0 3 MPa Max thermostat setting 30 85 C Pa...

Страница 27: ......

Страница 28: ...echnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de NIBE Energietechniek B V Postbus 2 4797 ZG WILLEMSTAD NB Tel 0168 477722 Fax 0168 476998 E m...

Отзывы: