33
ST-A1291-20-00
BOTTOM
GAS ENTRY
CONTROL VOLTAGE CUT HOLE
SIZED PER CHART
POWER ENTRY CUT HOLE
SIZED PER CHART
CONDUIT NUT
MAIN GAS
VALVE
EXTERNAL PIPING
SUPPLIED BY
OTHERS
GAS SUPPLY
SHUTOFF VALVE
POWER SUPPLY WIRE
(SIZED FROM MIN. CIRCUIT AMPACITY)
STRAIGHT CONDUIT FITTING
SIZED PER CHART
STRAIGHT CONDUIT FITTING FROM
POWER SUPPLY SIZED PER CHART
WIRE FROM
ZONE THERMOSTAT
STRAIGHT CONDUIT FITTING FROM
ZONE THERMOSTAT SIZED PER CHART
KNOCKOUTS FOR
HIGH VOLTAGE ENTRY
THERMOSTAT ROUTING
ENTRY HOLE
POWER ROUTING
ENTRY HOLE
Figure F.2. – A: Electrical and Piping Routing
F. CONTROL / THERMOSTAT WIRING
F.2. Routing Control wiring
Figure F.2. – B: Hole Sizing for Conduit
F.3. Measuring Control Voltage
Loads
Use a voltmeter to measure the low voltage and low voltage amp draws during operation. Accessories such as
remote smoke detectors and excessive wire length can increase the amp draw on the low voltage wiring. Verify
that the total amp draw on the 24Vac side is less than 0.3A in full operation.