107
P. APPENDICES
Appendix D – Reheat Data for (-)GEDZS 7.5 Ton
P. APPENDICES
$SSHQGL['5HKHDW'DWDIRU*('=67RQ
ENTERING INDOOR AIR @ 75°F [23.9°C] dbE
➀
wbE
65.3°F [18.5°C]
64°F [17.8°C]
62.5°F [16.9°C]
CFM [L/s]
1800 [850]
1700 [802]
1200 [566]
1800 [850]
1700 [802]
1200 [566]
1800 [850]
1700 [802]
1200 [566]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
60
[15.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
29.7 [8.7]
6.5 [1.9]
3.2
29.4 [8.6]
6.3 [1.8]
3.1
27.9 [8.2]
5.4 [1.6]
3.1
27.0 [7.9]
9.0 [2.6]
3.2
26.7 [7.8]
8.7 [2.6]
3.2
25.3 [7.4]
7.5 [2.2]
3.1
26.6 [7.8]
11.4 [3.4]
3.2
26.4 [7.7]
11.1 [3.3]
3.2
24.9 [7.3]
9.6 [2.8]
3.1
65
[18.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
29.5 [8.6]
5.0 [1.5]
3.2
29.2 [8.5]
4.9 [1.4]
3.2
27.6 [8.1]
4.2 [1.2]
3.1
26.7 [7.8]
7.6 [2.2]
3.3
26.4 [7.7]
7.4 [2.2]
3.2
25.0 [7.3]
6.3 [1.9]
3.2
26.4 [7.7]
10.0 [2.9]
3.2
26.1 [7.6]
9.7 [2.9]
3.2
24.7 [7.2]
8.4 [2.5]
3.1
70
[21.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
28.8 [8.4]
3.7 [1.1]
3.2
28.5 [8.4]
3.6 [1.0]
3.2
27.0 [7.9]
3.1 [0.9]
3.1
26.0 [7.6]
6.2 [1.8]
3.3
25.8 [7.6]
6.0 [1.8]
3.3
24.4 [7.1]
5.2 [1.5]
3.2
25.7 [7.5]
8.6 [2.5]
3.3
25.4 [7.5]
8.4 [2.5]
3.3
24.1 [7.1]
7.2 [2.1]
3.2
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
27.8 [8.1]
2.3 [0.7]
3.3
27.5 [8.1]
2.3 [0.7]
3.3
26.0 [7.6]
2.0 [0.6]
3.2
25.0 [7.3]
4.9 [1.4]
3.4
24.7 [7.2]
4.7 [1.4]
3.4
23.4 [6.9]
4.1 [1.2]
3.3
24.7 [7.2]
7.3 [2.1]
3.4
24.4 [7.2]
7.1 [2.1]
3.4
23.1 [6.8]
6.1 [1.8]
3.3
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
26.3 [7.7]
1.1 [0.3]
3.4
26.0 [7.6]
1.0 [0.3]
3.4
24.6 [7.2]
0.9 [0.3]
3.3
23.5 [6.9]
3.6 [1.0]
3.5
23.3 [6.8]
3.5 [1.0]
3.5
22.1 [6.5]
3.0 [0.9]
3.4
23.2 [6.8]
6.0 [1.8]
3.5
23.0 [6.7]
5.9 [1.7]
3.5
21.7 [6.4]
5.1 [1.5]
3.4
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
24.5 [7.2]
-0.2 [-0.1]
3.6
24.2 [7.1]
-0.2 [0.0]
3.6
22.9 [6.7]
-0.1 [0.0]
3.5
21.7 [6.4]
2.4 [0.7]
3.7
21.5 [6.3]
2.3 [0.7]
3.6
20.3 [6.0]
2.0 [0.6]
3.6
21.4 [6.3]
4.8 [1.4]
3.6
21.1 [6.2]
4.7 [1.4]
3.6
20.0 [5.9]
4.0 [1.2]
3.5
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
22.2 [6.5]
-1.3 [-0.4]
3.8
22.0 [6.4]
-1.3 [-0.4]
3.7
20.8 [6.1]
-1.1 [-0.3]
3.6
19.5 [5.7]
1.2 [0.3]
3.8
19.3 [5.6]
1.1 [0.3]
3.8
18.2 [5.3]
1.0 [0.3]
3.7
19.1 [5.6]
3.6 [1.1]
3.8
18.9 [5.5]
3.5 [1.0]
3.8
17.9 [5.3]
3.0 [0.9]
3.7
GROSS SYSTEMS PERFORMANCE DATA (LOW REHEAT MODE)—
GEDZS090
ENTERING INDOOR AIR @ 75°F [23.9°C] dbE
➀
wbE
65.3°F [18.5°C]
64°F [17.8°C]
62.5°F [16.9°C]
CFM [L/s]
3600 [1699]
2900 [1369]
2400 [1133]
3600 [1699]
2900 [1369]
2400 [1133]
3600 [1699]
2900 [1369]
2400 [1133]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
60
[15.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.7 [12.2]
8.9 [2.6]
5.0
39.9 [11.7]
8.0 [2.4]
4.9
38.7 [11.3]
7.4 [2.2]
4.8
40.1 [11.8]
12.8 [3.7]
4.9
38.4 [11.3]
11.5 [3.4]
4.8
37.2 [10.9]
10.5 [3.1]
4.8
40.0 [11.7]
18.5 [5.4]
4.9
38.3 [11.2]
16.7 [4.9]
4.8
37.1 [10.9]
15.3 [4.5]
4.8
70
[21.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.8 [11.7]
5.9 [1.7]
5.1
38.1 [11.2]
5.3 [1.6]
5.0
36.9 [10.8]
4.9 [1.4]
4.9
38.3 [11.2]
9.8 [2.9]
5.1
36.7 [10.7]
8.8 [2.6]
5.0
35.5 [10.4]
8.1 [2.4]
4.9
38.1 [11.2]
15.5 [4.6]
5.0
36.5 [10.7]
14.0 [4.1]
4.9
35.4 [10.4]
12.8 [3.8]
4.9
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.7 [10.7]
2.1 [0.6]
5.4
35.1 [10.3]
1.9 [0.5]
5.3
34.0 [10.0]
1.7 [0.5]
5.2
35.1 [10.3]
5.9 [1.7]
5.3
33.7 [9.9]
5.3 [1.6]
5.2
32.6 [9.6]
4.9 [1.4]
5.1
35.0 [10.3]
11.7 [3.4]
5.3
33.5 [9.8]
10.5 [3.1]
5.2
32.5 [9.5]
9.6 [2.8]
5.1
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
32.3 [9.5]
-2.7 [-0.8]
5.8
30.9 [9.1]
-2.4 [-0.7]
5.6
30.0 [8.8]
-2.2 [-0.6]
5.6
30.8 [9.0]
1.2 [0.3]
5.7
29.5 [8.6]
1.0 [0.3]
5.6
28.5 [8.4]
1.0 [0.3]
5.5
30.6 [9.0]
6.9 [2.0]
5.7
29.3 [8.6]
6.2 [1.8]
5.6
28.4 [8.3]
5.7 [1.7]
5.5
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
26.7 [7.8]
-8.3 [-2.4]
6.3
25.5 [7.5]
-7.4 [-2.2]
6.2
24.7 [7.3]
-6.8 [-2.0]
6.1
25.1 [7.4]
-4.4 [-1.3]
6.2
24.1 [7.1]
-4.0 [-1.2]
6.1
23.3 [6.8]
-3.7 [-1.1]
6.0
25.0 [7.3]
1.3 [0.4]
6.2
23.9 [7.0]
1.2 [0.4]
6.1
23.2 [6.8]
1.1 [0.3]
6.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
19.8 [5.8]
-14.7 [-4.3]
6.9
19.0 [5.6]
-13.2 [-3.9]
6.8
18.4 [5.4]
-12.2 [-3.6]
6.7
18.3 [5.4]
-10.9 [-3.2]
6.9
17.5 [5.1]
-9.8 [-2.9]
6.7
17.0 [5.0]
-9.0 [-2.6]
6.6
18.1 [5.3]
-5.1 [-1.5]
6.9
17.4 [5.1]
-4.6 [-1.4]
6.7
16.8 [4.9]
-4.2 [-1.2]
6.6
120
[48.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
11.7 [3.4]
-22.1 [-6.5]
7.8
11.2 [3.3]
-19.8 [-5.8]
7.6
10.8 [3.2]
-18.2 [-5.3]
7.5
10.1 [3.0]
-18.2 [-5.3]
7.7
9.7 [2.8]
-16.4 [-4.8]
7.5
9.4 [2.8]
-15.1 [-4.4]
7.4
10.0 [2.9]
-12.5 [-3.7]
7.7
9.6 [2.8]
-11.2 [-3.3]
7.5
9.3 [2.7]
-10.3 [-3.0]
7.4
GROSS SYSTEMS PERFORMANCE DATA (HIGH REHEAT MODE)—
GEDZS090
Содержание Climate Master RGED Series
Страница 2: ...2 62 ...
Страница 88: ...88 P APPENDICES Appendix C Air Flow Performance Data ...
Страница 90: ...90 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Страница 92: ...92 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Страница 94: ...94 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Страница 159: ...159 ...