Special instructions apply for power wiring with
aluminum conductors:
Warranty is void if connections are not made per
instructions.
Attach a length (6” or more) of recommended
size copper wire to the unit contactor terminals
L1, L2 and L3 for three phase.
Select the equivalent aluminum wire size from the
tabulation below:
Splice copper wire pigtails to aluminum wire with
U.L. recognized connectors for copper-aluminum
splices. Please exercise the following instructions
very carefully to obtain a positive and lasting
connection:
1. Strip insulation from aluminum conductor.
2. Coat the stripped end of the aluminum wire
with the recommended inhibitor, and wire
brush the aluminum surface through inhibitor.
INHIBITORS: Brundy-Pentex “A”; Alcoa-No.
2EJC; T & B-KPOR Shield.
3. Clean and recoat aluminum conductor with
inhibitor.
4. Make the splice using the above listed wire
nuts or split bolt connectors.
5. Coat the entire connection with inhibitor and
wrap with electrical insulating tape.
NOTE:
Wiring to be done in the field between
the unit and devices not attached to the unit,
or between separate devices which are field
installed and located, shall conform with the
temperature limitation for Type T wire [63°F rise
(35°C)] when installed in accordance with the
manufacturer’s instructions.
E.1.2. 208/240 Volt Operation and
Required Adjustments
E.1.2.1.Low Voltage Transformer Tap
Adjustment for 208Volt
Transformer is factory wired for 230 volts on 208-
230 volt models and must be changed for 208
volt applications. See unit wiring diagram for 208
volt wiring.
E. ELECTRICAL
Содержание Climate Master RGED Series
Страница 2: ...2 62 ...
Страница 88: ...88 P APPENDICES Appendix C Air Flow Performance Data ...
Страница 90: ...90 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Страница 92: ...92 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Страница 94: ...94 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Страница 159: ...159 ...