Temperature sensor, on
supply pipeline
Temperature sensor on supply pipeline (BT25) must
be connected: for SMO 20 to clamps X2:8 and X2:10,
while for SMO 40 to clamps X6:5, X6:6. Use a two-
wire cable with the cross-section of at least 0.5 mm².
Temperature sensor on the supply pipeline at
the heating module upstream the isolation valve
(QN10)
Temperature sensor on the pipeline downstream the
heating module (BT63) must be connected in SMO
20 to clamps X2:9 and X2:10, while in SMO 40 to
AUX clamps, e.g.: X6:13 and X6:14, and then turn on
sensor power supply - see SMO40 installation man-
ual. Use a two-wire cable with the cross-section of at
least 0.5 mm².