14
HK 200S
HK 200S-6
Pipe dimensions and materials
HK 200S
Gas pipe
Liquid pipe
Pipe replacement
Ø15,88 mm (5/8”) Ø9,52 mm (3/8”)
Connection
Connection– (5/8”) Connection–(3/8”)
Material
Quality of copper SS-EN 12735-1 or
C1220T, JIS H3300
Minimum ma-
terial thickness
1.0 mm
0.8 mm
HK 200S-6
Gas pipe
Liquid pipe
Pipe replacement
Ø12.7 mm (1/2”)
Ø6,35 mm (1/4”)
Connection
Connection– (1/2") Connection–(1/4”)
Material
Quality of copper SS-EN 12735-1 or
C1220T, JIS H3300
Minimum ma-
terial thickness
1.0 mm
0.8 mm
Pipe connection
•
Execute the pipe installation with the mainte
-
nance valves (QM35, QM36) closed.
AMS 10-6 / AMS 10-8
•
Remove the side panel on AMS 10 during the in-
stallation to make access easier.
Socket connections
Extension:
Shift:
LEK
LEK
Przód
Elementy do wybicia
IMPORTANT
When soldering, apply the shielding gas.
Chapter 4 |
Pipe connections
Outer
diameter ,
copper pipe
(mm)
B, using the
R410A tool
(mm)
B, using a con-
ventional tool
(mm)
Ø 9,52
0,0~0,5
0,7~1,3
Ø 15,88
Ø 6,35
1,0~1,5
Ø 12,7
External
diameter, cop-
per pipe (mm)
Torque
(Nm)
Tighten-
ing angle
(°)
Recom-
mended tool
length
(mm)
Ø6,35
14~18
45~60
100
Ø 9,52
34~42
30~45
200
Ø12,7
49~61
30~45
250
Ø 15,88
68~82
15~20
300
AMS 10-12
•
Remove the “to be removed” part from the exter
-
nal panel at the AMS 10 mode where pipes are
to be led. The drawing below presents exemplary
pipe outlets.
•
Make sure that no water or dirt can permeate to
the pipes.
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
External diameter, copper pipe
A (mm)
Ø 6,35
9,1
Ø 9,52
13,2
Ø 12,7
16,6
Ø 15,88
19,7
HK 200S
HK 200S-6
•
Bend pipes with maximum bending radius (at
least R100~R150). Do not bend pipes many
times. Use a bending machine.
•
Connect the socket connection and tighten with
appropriate torque. Apply the appropriate tight
-
ening angle if the torque wrench is not available.