6.10
MS-2102
Chapter 6
Setpoint Values
MESSAGE NO:
S3-08
APPLIES TO:
Control Module
DEFAULT VALUE: off
VALUE RANGE: on, off
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function staggers the power up of heater circuits to eliminate tripping of the
main breaker. If this value is set to “on”, the second heater will be turned on one
minute after the power up if the circuit is calling for heat.
MESSAGE NO:
S3-09
APPLIES TO:
Control Module
DEFAULT VALUE: 1200
VALUE RANGE: 600,1200,2400,4800,9600
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function sets the communication baud rate for the RS-485 serial port. All controllers
connected to the same data highway must operate at the same baud rate.
MESSAGE NO:
S3-10
APPLIES TO:
Control Module
DEFAULT VALUE: alarm:off
VALUE RANGE: alarm:off, alarm:on
flash/on, flash/off
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function determines the response of the alarm light output to an alarm. The alarm
light output is design to drive a 5Vdc LED. If the value is set to
alarm off
, the alarm
light is
on
in a no alarm condition and turns
off
when alarms are present. The
alarm off
setting works best with a green LED for fail-safe mode where loss of power or a burnt
out LED generates an alarm condition. Value
alarm on
, turns the alarm light
off
in a no
alarm condition and turns
on
when alarms are present. Value
alarm flash/on
flashes
the alarm light when alarms are present and turns
on
the alarm light when there are no
alarms. Value
alarm flash/off
flashes the alarm light when alarms are present and
turns
off
the alarm light when there are no alarms.
MESSAGE NO:
S3-11
APPLIES TO:
Control Module
DEFAULT VALUE: MECH:NC
VALUE RANGE: MECH:NO SS:N/A
SS:N/A
MECH:NO SS:N/A
MECH:NC SS:N/A
MECH:NC SS:N/A,
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function configures the alarm contacts for normally open (NO) or normally
closed (NC). MECH refers to the mechanical alarm contact on terminals 20 and 21 of
the Control Module. SS refers to the solid state alarm contact that is not available on
board. In
NO
mode, the contact closes during alarm condition. In
NC
mode, the
contact opens during alarm condition.
MESSAGE NO:
S3-12
APPLIES TO:
Control Module
DEFAULT VALUE: 1
VALUE RANGE: 1-250
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function changes the Module Number of the Control Module. If a controller is to
communicate along with other modules to a central computer or display, each module
must have a unique address to ensure only one module attempts to communicate
with the remote display at any time. The address for communication is the module
number.
MESSAGE NO:
S3-13
APPLIES TO:
Control Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This message displays the firmware version number.
FIRMWARE VERSION
D0-00-00
STAGGER START:
off
BAUD RATE:
1200
ALARM LIGHT MODE:
alarm: off
SET MODULE
NUMBER: 1
ALARM CONTACTS:
MECH:NO
SS:N/A
Содержание MASTERTRACE MS-2102
Страница 1: ...MASTERTRACE MS 2102 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 10: ...MS 2102 1 7 Chapter 1 Product Overview Figure 1 5 Hardware Block Diagram ...
Страница 12: ...2 2 MS 2102 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 22: ...4 2 MS 2102 Chapter 4 Front Panel Operation Figure 4 1 Display Front View Figure 4 2 Contrast Control ...