MS-2102
6.9
Chapter 6
Setpoint Values
MESSAGE NO:
S3-01
APPLIES TO:
Control Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE: All
RESTRICTIONS: None
This message displays the name of the sub-menu when entered.
MESSAGE NO:
S3-02
APPLIES TO:
Control Module
DEFAULT VALUE: advanced user
VALUE RANGE: advanced
user, normal user
DISPLAY MODE:
All
RESTRICTIONS: None
This function determines what messages are displayed. If set to
advanced user
, all
messages are displayed. If set to
normal user
, only the basic messages are displayed.
Each message listed in this chapter shows the Display Mode required to see the
message.
Advanced
indicates that you must set the display mode to
advanced user
to
view the message.
MESSAGE NO:
S3-03
APPLIES TO:
Control Module
DEFAULT VALUE: System status VALUE RANGE: See values below
DISPLAY MODE:
Advanced
RESTRICTIONS: Heater Temp messages are
not displayed if Heater
setpoint is
off
.
This function specifies the information that will be displayed when no key has been
pressed for the Display Timeout interval as described below.
VALUE
INFORMATION DISPLAYED
System status
Alarm status
Heater status
Heater on or off
Heater temp
Control temperature
MESSAGE NO:
S3-04
APPLIES TO:
Control Module
DEFAULT VALUE: 60 s
VALUE RANGE: 5 to 600 s, off
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function sets the length of time, from the last key press, to automatically return
to the Default Display information. To disable this function, set the value to
off
.
MESSAGE NO:
S3-05
APPLIES TO:
Control Module
DEFAULT VALUE: 3 s
VALUE RANGE: 1 to 10 s
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function sets the length of time between the display of successive messages.
Select a value that is comfortable for the viewing speed of the operator.
MESSAGE NO:
S3-06
APPLIES TO:
Control Module
DEFAULT VALUE: Celsius
VALUE RANGE: Celsius, Fahrenheit
DISPLAY MODE:
Advanced
RESTRICTIONS: Heater Setpoint must not be
off
.
This function sets the units of measure for temperature. All temperatures are displayed
in the selected units of either degrees Celsius (°C) or degrees Fahrenheit (°F).
MESSAGE NO:
S3-07
APPLIES TO:
Control Module
DEFAULT VALUE: $0.05
VALUE RANGE: $0.01 to $0.50
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function sets the COST PER kWh. The controller uses this value to calculate
Energy Cost.
System Setup
COST PER kWh:
$0.05
DEFAULT DISPLAY:
System Status
DISPLAY TIMEOUT:
60 seconds
SCAN TIME:
2 seconds
TEMPERATURE UNITS:
Celcius
DISPLAY MODE:
advanced user
SETPOINTS:
SYSTEM SETUP
Содержание MASTERTRACE MS-2102
Страница 1: ...MASTERTRACE MS 2102 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 10: ...MS 2102 1 7 Chapter 1 Product Overview Figure 1 5 Hardware Block Diagram ...
Страница 12: ...2 2 MS 2102 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 22: ...4 2 MS 2102 Chapter 4 Front Panel Operation Figure 4 1 Display Front View Figure 4 2 Contrast Control ...