5.4
MS-2102
Chapter 5
Measured Values
MESSAGE NO:
M2-13
APPLIES TO:
Control Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE:
Advanced
RESTRICTIONS: None
MESSAGE NO:
M2-14
APPLIES TO:
Control Module
DEFAULT VALUE: HT M-1
VALUE RANGE: HT M-1 to M-2
DISPLAY MODE:
All
RESTRICTIONS: None
This function selects the heater circuit. Each heater circuit has a unique Heater
Number in a form of M-N. M is the Module Number of the Control Module and N
is the heater circuit within the Control Module. Press [VALUE
×
] or [VALUE
Ø
]
and then press [STORE] to select a heater circuit. For convenience and to reduce
human error, the Heater Name is also displayed.
MESSAGE NO:
M2-15
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: -50 to 500 °C
-58 to 932 °F, RTD Short
DISPLAY MODE:
Advanced
RESTRICTIONS: Heater Setpoint is not
off
.
The displayed value is the lowest Measured Temperature since the last reset. If the
displayed value is
RTD Short
, a value less than the minimum range was recorded.
To reset the displayed value press [RESET]. To reset with all statistics, use RESET
STATISTICS.
MESSAGE NO:
M2-16
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: -50 to 500 °C
-58 to 932 °F, RTD Open
DISPLAY MODE:
Advanced
RESTRICTIONS: Heater Setpoint is not
off
.
The displayed value is the highest Measured Temperature since the last reset. If
the displayed value is
RTD OPEN
, a value greater than the maximum range was
recorded. To reset the displayed value, press [RESET]. To reset with all statistics,
use RESET STATISTICS.
MESSAGE NO:
M2-17
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0.1 to 30.0/100.0 A, O.L.
DISPLAY MODE:
Advanced
RESTRICTIONS: None
The displayed value is the highest heater/phase-A current since the last reset. If
the displayed value is
O.L.
, a value greater than the maximum range was recorded.
To reset the displayed value, press [RESET]. To reset with all statistics, use RESET
STATISTICS.
MESSAGE NO:
M2-18
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0.1 to 100.0 A, O.L.
DISPLAY MODE:
Advanced
RESTRICTIONS: None
The displayed value is the highest heater phase-B current since the last reset. If
the displayed value is
O.L.
, a value greater than the maximum range was recorded.
To reset the displayed value, press [RESET]. To reset with all statistics, use RESET
STATISTICS.
MESSAGE NO:
M2-19
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0.1 to 100.0 A, O.L.
DISPLAY MODE:
Advanced
RESTRICTIONS: None
The displayed value is the highest heater phase-C current since the last reset. If
the displayed value is
O.L.
, a value greater than the maximum range was recorded.
To reset the displayed value, press [RESET]. To reset with all statistics, use RESET
STATISTICS.
MAX HEATER
CURRENT: 4.7A
MAX TEMPERATURE:
25°C
MEASURED:
STATISTICS
Statistics
SELECT HT M-1
"
NONAME
MIN TEMPERATURE:
3°C
B: MAX HEATER
CURRENT: 4.7A
C: MAX HEATER
CURRENT: 4.7A
Содержание MASTERTRACE MS-2102
Страница 1: ...MASTERTRACE MS 2102 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 10: ...MS 2102 1 7 Chapter 1 Product Overview Figure 1 5 Hardware Block Diagram ...
Страница 12: ...2 2 MS 2102 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 22: ...4 2 MS 2102 Chapter 4 Front Panel Operation Figure 4 1 Display Front View Figure 4 2 Contrast Control ...