5.2
MS-2102
Chapter 5
Measured Values
MESSAGE NO:
M1-01
APPLIES TO:
Control Module
DEFAULT VALUE: N/A
VALUE RANGE: N/A
DISPLAY MODE: All
RESTRICTIONS: None
MESSAGE NO:
M1-02
APPLIES TO:
Control Module
DEFAULT VALUE: HT M-1
VALUE RANGE: HT M-1 to M-2
DISPLAY MODE:
All
RESTRICTIONS: None
This function selects the heater circuit. Each heater circuit has a unique Heater
Number in a form of M-N. M is the Module Number of the Control Module and N
is the heater circuit within the Control Module. Press [VALUE
×
] or [VALUE
Ø
]
and then press [STORE] to select a heater circuit. For convenience and to reduce
human error, the Heater Name is also displayed.
MESSAGE NO:
M1-03
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: on, off, man on,
no: 1 to 9 alarms
DISPLAY MODE: All
RESTRICTIONS: None
The displayed value is the status of the selected heater. It indicates whether the
heater circuit is on or off and the number of alarm messages associated with the
circuit. The heater is forced on by HEATER TEST function if
man on
is displayed.
See HEATER TEST function.
MESSAGE NO:
M1-04
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: -50 to 500 °C, RTD Open
-58 to 932 °F, RTD Fault
DISPLAY MODE:
All
RESTRICTIONS: Heater Setpoint must not be
off
or
none
.
MS-2102 calculates the displayed value based on the actual measured temperature
of the selected heater’s RTD. MS-2102 controls the selected heater circuit by
comparing the Heater Control Temperature to the Heater Setpoint. If the tempera-
ture is outside the value range, then
RTD OPEN
or
RTD SHORT
is displayed.
MESSAGE NO:
M1-05
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: -50 to 500 °C, RTD A Open
-58 to 932 °F, RTD A Fault
DISPLAY MODE:
All
RESTRICTIONS: Dual RTD per circuit mode
The displayed value is the actual measured temperature of RTD-A sensor for the
heater circuit. It is used to calculate the Heater Control Temperature based oo the
RTD MODE. If the temperature is outside the value range, then
RTD A OPEN
or
RTD A SHORT
is displayed.
MESSAGE NO:
M1-06
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: -50 to 500 °C, RTD B Open
-58 to 932 °F, RTD B Fault
DISPLAY MODE:
All
RESTRICTIONS: Dual RTD per circuit mode
The displayed value is the actual measured temperature of RTD-B sensor for the
heater circuit. It is used to calculate the Heater Control Temperature based oo the
RTD MODE. If the temperature is outside the value range, then
RTD B OPEN
or
RTD B SHORT
is displayed
Operating
MEASURED:
OPERATING VALUES
HEATER CONTROL
TEMP: 6°C
HEATER IS ON
NO ALARMS
SELECT HT M-1
"
NONAME
RTD-A ACTUAL
TEMP: 6°C
RTD-B ACTUAL
TEMP: 6°C
Содержание MASTERTRACE MS-2102
Страница 1: ...MASTERTRACE MS 2102 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 10: ...MS 2102 1 7 Chapter 1 Product Overview Figure 1 5 Hardware Block Diagram ...
Страница 12: ...2 2 MS 2102 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 22: ...4 2 MS 2102 Chapter 4 Front Panel Operation Figure 4 1 Display Front View Figure 4 2 Contrast Control ...