Chapter 7 Alarms
Process Alarms
The Heater Control Temperature is greater than or equal to the High Temperature
Alarm setpoint.
ü
Check that the alarm setpoint is correct.
ü
Test for correct RTD operation.
ü
Check the heat trace design.
The Heater Control Temperature is less than or equal to the Low Temperature
Alarm setpoint.
ü
Check that the alarm setpoint is correct.
ü
Test for correct RTD operation.
ü
Check for damaged insulation or cladding.
ü
Check for damaged heat trace.
ü
Check the heat trace design.
The measured Heater Current, when the heater circuit is on, is greater than or
equal to the High Current Alarm setpoint or, the Heater Current is greater than the
maximum value range.
ü
Check that the alarm setpoint is correct.
ü
For self-regulating heating cable, the current varies substantially with tempera-
ture. Check that the alarm setpoint accounts for this variation or use the heat
trace curve function.
ü
Test for correct current measurement.
The measured Heater Current, when the heater circuit is on, is less than or equal
to the Low Current Alarm setpoint.
ü
Check that the alarm setpoint is correct.
ü
For self-regulating heating cable, the current varies substantially with tempera-
ture. Check that the alarm setpoint accounts for this variation or use the heat
trace curve function.
ü
Test for correct current measurement.
ü
For parallel resistance heating cable, check for broken cable, failed splice or
tee connection.
ü
For zone-type heating cable, check for failed zones.
The measured circuit voltage is less than or equal to the Low Voltage Alarm
setpoint.
ü
Check for voltage input failure by measuring the voltage at the Heater Voltage
terminals.
ü
If a control transformer is used for input power, check wiring configuration to
the transformer.
ü
Check loading on power system. Possible brown out.
One of the following alarms occurred during the TraceCheck™ cycle. Refer to the
alarm details above for the individual alarm.
ü
TC SWITCH SHORTED ALARM
ü
TC LOSS OF CONTINUITY
ü
TC HIGH CURRENT ALARM
ü
TC LOW CURRENT ALARM
ü
TC GROUND FAULT ALARM
ü
TC GROUND FAULT TRIP
HIGH TEMPERATURE
ALARM
LOW TEMPERATURE
ALARM
HIGH CURRENT
ALARM
LOW CURRENT
ALARM
LOW VOLTAGE
ALARM
Warning Alarms
ALARM DURING
TRACECHECK
Содержание MASTERTRACE MS-2102
Страница 1: ...MASTERTRACE MS 2102 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 10: ...MS 2102 1 7 Chapter 1 Product Overview Figure 1 5 Hardware Block Diagram ...
Страница 12: ...2 2 MS 2102 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 22: ...4 2 MS 2102 Chapter 4 Front Panel Operation Figure 4 1 Display Front View Figure 4 2 Contrast Control ...