5.6
MS-2102
Chapter 5
Measured Values
HEATER IS ON
17% OF THE TIME
TIME SINCE RESET
48 hrs
RESET STATISTICS?
no
"
ARE YOU SURE?
no
"
MESSAGE NO:
M2-27
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 100%
DISPLAY MODE:
Advanced
RESTRICTIONS: None
The displayed value is the percentage of time that the heater circuit has been on
since the last reset. PERCENT ON TIME = HEATER ON TIME ÷ TIME SINCE
RESET x 100%. It indicates how active the heater circuit is and can be useful for
maintenance. Interpretation of this value depends on the process but large
changes could be an indication of degradation of the heater or the insulation. To
reset, use RESET STATISTICS.
MESSAGE NO:
M2-28
APPLIES TO:
Control Module
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 999,999 hours
DISPLAY MODE:
Advanced
RESTRICTIONS: None
The displayed value is the total time since the last reset. It is useful for
maintenance purpose. To reset, use RESET STATISTICS.
MESSAGE NO:
M2-29
APPLIES TO:
Control Module
DEFAULT VALUE: N/A
VALUE RANGE: yes, no
DISPLAY MODE:
Advanced
RESTRICTIONS: None
This function resets all the statistical values. Select
yes
and then press [STORE].
You are asked to confirm your request. Again, select
yes
and then press [STORE].
The statistical values are now cleared.
Содержание MASTERTRACE MS-2102
Страница 1: ...MASTERTRACE MS 2102 OPERATOR S MANUAL HEAT TRACING CONTROL ...
Страница 10: ...MS 2102 1 7 Chapter 1 Product Overview Figure 1 5 Hardware Block Diagram ...
Страница 12: ...2 2 MS 2102 Chapter 2 Installation Figure 2 2 Power Board Layout Figure 2 1 Main Board Layout ...
Страница 22: ...4 2 MS 2102 Chapter 4 Front Panel Operation Figure 4 1 Display Front View Figure 4 2 Contrast Control ...