Site Wiring Fault
Alarm Code: 04
Site Fault detection is
supported on all models
anytime there is a
Grounding Neutral
connection.
Alarm triggers when the
difference between
ground and neutral
voltage is > 15v.
Site Fault detection should
be enabled by default. It can
still be enabled / disabled
from the LCD settings
menu.
Reconnect all input wires
Utility Abnormal
Alarm Code: 02
Utility is out of the
tolerance of input
Check input mains condition
Back feed
Alarm Code:93
UPS has a unexpected
bypass current on battery
mode
Transfer to maintenance
bypass and call service.
Battery Disconnect
Alarm Code:11
Battery voltage is lower
than the batteries
disconnected level
defined for this UPS. This
may be due to a blown
fuse, intermittent battery
connection or battery
cable being
disconnected.
Verify that all batteries are
properly connected.
If the condition persists,
contact your service
representative.
Battery low
Alarm Code:12
The UPS is in Battery
mode and the battery is
running low
This warning is
approximate, and the actual
time to shutdown may vary
significantly.
Depending on the UPS load
and number of Extended
Battery (E
XB
s), the “Battery
Low” warning may occur
before the batteries reach
25% capacity
Service Battery
Alarm Code:13
A faulted battery string
has been detected and as
a result the battery
charger has been
disabled until it is
replaced
Contact your service
representative
Содержание LOGIX II RT NETPACK 10000VA
Страница 1: ...NEXT UPS Systems LOGIX II RT 6000 10000 NETPACK Installation and user manual English...
Страница 4: ......
Страница 31: ...www nextups eu 27 English Figure 4 5 a Parallel systerm wiring diagram of LOGIX II 6000 1000...
Страница 32: ...www nextups eu 28 English Figure 4 5 b Parallel System Installation Diagram...
Страница 43: ...www nextups eu 39 English...