NIO200 HAG User Guide
Page 58 of 120
state of the Wireless Hart communication. The value should be
interpreted as 16 bit big-endian integer with the following values:
128: Device Joined with fresh data
8: Device NOT joined and no data read so far
20: Device NOT joined but with stale data
24: Device Joined but no data read so far
4: Device Joined but with stale data
When register type
is “gw_info”, general gateway information will be exposed to Modbus,
using the following registers:
Register
Item exposed
Observation
<start_addr> + 0
Number of devices currently
16bit big-endian integer
connected.
<start_addr> + 1
Total number of burst messages. 16bit big-endian integer
<start_addr> + 2
Versa Router MAC
3 words * 16bit big-endian
unsigned integer
Note: For
register type “gw_info” the <word_cnt> must be 5.
When
register type is “gw_code_word”, the gateway’s “code word” will be exposed to Modbus. The
“code word” is read-only.
Note
: For register type “gw_code_word”, the <word_cnt> should be 16 or less.
The <EUI64> in “gw_info” and “gw_code_word” register lines should identify the WirelessHart
Gateway.
Accepted values: 001B1EF981000002, 0000000000000000, FFFFFFFFFFFFFFFF.
2.
Click
Save
to add the new register line in the Registers list.
Содержание NIO200 HAG
Страница 1: ...NIO200 HAG WirelessHART All in One Gateway User Guide Version 1 2 Date March 17 2017 ...
Страница 12: ...NIO200 HAG User Guide Page 12 of 120 Figure 1 ...
Страница 72: ...NIO200 HAG User Guide Page 72 of 120 Appendix Advanced configuration about Wi Fi features ...
Страница 89: ...NIO200 HAG User Guide Page 89 of 120 ...
Страница 112: ...NIO200 HAG User Guide Page 112 of 120 TFTP Settings By default TFTP server is not enabled ...