NIO200 HAG User Guide
Page 59 of 120
Note: For
register type “gw_info” the <word_cnt> must be 5.
When regist
er type is “gw_code_word”, the gateway’s “code word” will be exposed to Modbus. The
“code word” is read-only.
Note
: For register type “gw_code_word”, the <word_cnt> should be 16 or less.
The <EUI64> in “gw_info” and “gw_code_word” register lines should identify the WirelessHart
Gateway.
Accepted values: 001B1EF981000002, 0000000000000000, FFFFFFFFFFFFFFFF.
3.
Click
Save
to add the new register line in the Registers list.
Notes:
When mapping the Modbus registers on the WirelessHART data entities, you must consider
the size of the WirelessHART data entity and allocate a contiguous chunk of Modbus 16-bit
registers in the Modbus addressing space to hold the entire data entity (plus an additional
Modbus register to hold the auto-generated status, if applicable). When the chunk is bigger
than the size of the data entity, it will be filled with the actual data from the lowest addressed
register to the highest, and from the MSB of each register to the LSB. If the data entity does
not entirely fill the last register, the register will have the data on the MSB and the LSB will be
set to zero.
If the address range of a register line overlaps an existing register line in the same group, or if
it does not fit in the range 0-65535, it will be ignored
Loading a List of Registers
You can import the register map from a file that includes the input and holding registers lines with
their parameters which are expressed as comma separated values.
To load the list:
Содержание NIO200 HAG
Страница 1: ...NIO200 HAG WirelessHART All in One Gateway User Guide Version 1 2 Date March 17 2017 ...
Страница 12: ...NIO200 HAG User Guide Page 12 of 120 Figure 1 ...
Страница 72: ...NIO200 HAG User Guide Page 72 of 120 Appendix Advanced configuration about Wi Fi features ...
Страница 89: ...NIO200 HAG User Guide Page 89 of 120 ...
Страница 112: ...NIO200 HAG User Guide Page 112 of 120 TFTP Settings By default TFTP server is not enabled ...