Parameter Descriptions Table (All levels are user-programmable. Some values are interdependent.)
AVR Function
Disable
AVR Function Enable
Default
Setting
Selections or
Selectable
Range
Default
Setting
Selections or
Selectable
Range
50.
Buck Function
√
51.
Boost Function
√
52.
Sense Type
Normal
Normal
Normal
Normal
Generator
UPS
Generator
UPS
53.
Line Qualify Time
Battery to Line
--------------------
30s
3s
30s
3s
10s
10s
30s
30s
54.
Line High
When input voltage exceeds this level, unit
transfers to Battery Mode from either Buck
Mode (when AVR is enabled) or Line mode.
Line to Battery
--------------------
130VAC
120~152V
AC
152V AC
120~152V AC
55.
Line Low
When input voltage is lower than this level,
unit transfers to Battery Mode from either Boost
Mode (when AVR is enabled) or Line Mode.
Line to Battery
--------------------
100VAC
88~120V AC
88V AC
88~120V AC
56.
Boost Low
When input voltage drops between Boost Back
point and Boost Low point, unit will transfer to
Boost Mode only when AVR is enabled.
Normal to Boost
--------------------
[DISABLE]
102V AC
96~120V AC
57.
Buck High
When input voltage increases between Buck
High point and Buck Back point, unit will
transfer to Buck Mode only when AVR is
enabled.
Normal to Buck
--------------------
[DISABLE]
128V AC
120~144V AC
58.
High Gap
5VAC
3~7V AC
5VAC
3~7V AC
59.
Low Gap
5VAC
3~7V AC
5V AC
3~7V AC
* High Back
When input voltage drops below this level,
unit transfers back to Line Mode from Battery
Mode.
Battery to Line
--------------------
( Line High - High Gap )
( Line High - High Gap )
* Low Back
When input voltage rises above this level, unit
transfers back to the Line Mode from Battery
Mode.
Battery to Line
--------------------
( Line Low + Low Gap )
( Line Low + Low Gap )
* Boost Back
When input voltage rises above this level, unit
transfers to Normal Mode.
Boost to Normal
--------------------
[DISABLE]
( Boost Low + Low Gap )
* Buck Back
When input voltage drops below this level,
unit transfers back to the Normal Mode.
Buck to Normal
--------------------
[DISABLE]
( Buck High - High Gap )