5.6.10 Event Log View
Menu 7 lists the Event log status.
To access Event Log menu, type 7 and press Enter on the main menu. To return to the main menu, press Esc and then
press Enter.
[7 – Event Log View]
70. Display Event Log Records
Display the history event log records.
The maximum log number is 200.
71. Reset Event Log
Clear all the event log records.
5.7 *SNMP card
This is an optional communication function for UPS over a company intranet or the internet via a web browser. Please
refer to SNMP user manual for more information.
6. SPECIFICATIONS
6.1 Line Mode Specifications
Model
AC-UPS-48-2000
AC-UPS-48-1500
AC-UPS-48-1200
AC-UPS-24-700
Power factor
0.8
1.0
Nominal battery voltage
48V DC
24V DC
Utility Voltage Waveform
Sinusoidal (utility or generator)
Utility qualify time setting
3/10/30 seconds adjustable,
Nominal Input Voltage
120V AC
AVR function
Enable/ Disable
Utility voltage range
88 ~152 V AC user programmable.
Defaults set @ 100 ~ 130V AC
Nominal Input Frequency
50Hz / 60Hz (Auto detection, 55Hz as boundary)
Default frequency
Last utility frequency
Utility frequency range
47 ~ 53 Hz (50Hz mode) / 57 ~ 63Hz (60Hz mode)
Transfer Time
UPS without MBS
UPS mode
5ms typical
Normal mode
20ms typical
Generator mode
20ms typical
UPS with MBS
40ms maximum
Overload Protection
5s @≥ 125 ~150% load; 60s @110% ~ 125% load
Output short circuit
Input/Output Breaker
Site fault detection
Yes
Efficiency (Line mode)
95%
Efficiency (AVR mode)
90%
External MBS power capacity
30A
External MBS
When UPS is good, the MBS allows UPS output to flow out to the outdoor cabinet. If the
UPS is not functioning, the MBS will bypass the UPS allowing the utility to flow out to the
outdoor cabinet.