-28-
7-4. Test Mode
Setting
Use the test stick to press the TEST switch to enter the test mode. The TEST switch is pressed to turn the
test mode on and off. The test mode will automatically end in 10 minutes.
Operation
―TEST‖ will be displayed on the LCD.
While in the test mode, it is possible to change the analog output (4
–20mA) to the desired value with 0.16 mA
increments (1% of the full scale value). Increase or decrease the analog output value by pressing the UP or
DOWN button.
Increase/decrease the analog output value
using UP/DOWN button.
Turn on/off the recessed TEST switch with
test stick.
CAUTION
While in the test mode (alarm test using the TEST switch), the gas alarm contacts activate. If
the gas alarm contacts are used to operate the interlocks, etc. of the external devices, release
the interlocks, etc. beforehand, as needed, to prevent a possible activation of the interlocks
during the test mode, or
Enter the maintenance mode before entering the test mode. Release the interlocks of the
external devices beforehand, if needed (refer to 7-
5. ―Maintenance Mode‖).
Notify those concerned before starting a gas alarm test.