NTI Secure Remote Power Reboot Switch
6
Terminal Connection for RS232
To make a direct serial connection to the IPDU-Sx from a terminal with HyperTerminal via RS232, an RJ45 female DCE port
labeled "Console" is provided. Connect a CAT5 patch cable (supplied) between the port labeled “Console” and a PC with a
terminal program (e.g. HyperTerminal). An adapter (supplied) may need to be used to connect the patch cable to the PC.
Figure 3- Connect IPDU-S2 to local terminal
Sensor Attachment
The IPDU-Sx is capable of sensing and reporting readings taken from ENVIROMUX temperature (ENVIROMUX-STS), humidity
(ENVIROMUX-SHS), temperature/humidity (ENVIROMUX-STHS), wide range temperature/humidity (ENVIROMUX-STHS-99) and
liquid detection (ENVIROMUX-LDTx-y) sensors. Any of these can be connected to the “RJ45 Sensors” ports and used to
determine if connected devices should be powered ON or OFF based on readings taken. The maximum CAT5 cable length for
attachment of sensors is 1000 feet. For the cable pinout, see page 108.
Figure 4- Connect sensors for environmental monitoring
Terminal
DB9 male
connector
RJ45F-to-DB9F Adapter
(supplied)
CAT5 Patch Cable
Power
1
2
Outlet
Fault
Sensor
IP
Reset
RJ45 Sensors
Console
Ethernet
NTI
R
Network Technologies Inc
ENVIROMUX
R
Fault
Power
1
2
Outlet
Fault
Sensor
IP
Reset
RJ45 Sensors
Console
Ethernet
NTI
R
Network Technologies Inc
ENVIROMUX
R
Fault
ENVIROMUX-STS
Temperature
Sensor
ENVIROMUX-SHS
Humidity
Sensor
CAT5 Cable- maximux 1000 feet