8
Neptronic
®
www.neptronic.com
Evaporative Humidification / Cooling System
When designing or installing an air handling system that incorporates an ‘SK VAP’, appropriate
micro-organism and bacterial control methods MUST be considered and this should only be undertak
en by suitably qualified persons. A risk assessment MUST also be undertaken in relation to control of
micro-organisms and bacterial growth, especially Legionnaires disease.
If in doubt and for further information, contact Neptronic
®
Description Specification
SK VAP Control panel
Module Construction
Evaporative Material
Water Pump
Water Inlet Size
Water Inlet Control
Water Drain Size
Water Drain Control
Water Inlet Flow and Pressure
Max. Inlet Water Pressure
Max. Inlet Water Temperature
Water Consumption
Anti-bacterial Control
Modulating Control Option
Microprocessor control panel
Stainless Steel
inorganic and inflammable material UL900 class 1, Safe & hygienic resist-
ance to fungi according to JIS L 1902, ASTM G26-96 (2002)
Immersion Pump 110/230 V 50/60 Hz
IP 55 CE UL CSA Approved
1/2” (15mm) Pipe-work
Inlet Solenoid Valve
Float Switch
Float Valve
3/4” (20mm) Drain Outlet
Motorised two port n/o valve 24Vac
31 lb/m (14 l/m) @ 29 psi (2 bar)
101 psi (7 bar)
68º F (20º C)
Humidification duty + cleaning cycle usage.
(Refer to cleaning cycle section of the manual)
Note; For module dimensions and weight refer to dimensions and weights
section
PureFlo Ag+ Silver Cartridge and 5 micron sediment filter
2 Stage (1 Solenoid valve)
3 Stage (2 Solenoid valves)
4 Stage (3 Solenoid valves)
Matrix
Distribution
Header
Re-circulating
Pump
Drain Assembly
Tank
Dim A Width
(See tables at the back
of this manual).
Di
m
B
He
ig
ht
(S
ee
ta
bl
es
at
th
e
ba
ck
of
th
is
m
an
ua
l).
2”
(5
0m
m
)
Up
st
an
d
No
tS
up
pl
ie
d
18”
(445mm)
Tank
24”
(575mm)
O/All Depth
Matrix depth
(See tables at
the back of this
manual).
Caution:
The unit must be installed on a minimum
2” (50mm) upstand to ensure gravity drainage.
Typical Evaporative Module Overview
SK VAP Module Specification
Содержание SK VAP
Страница 4: ...4 Neptronic www neptronic com Evaporative Humidification Cooling System...
Страница 17: ...17 Neptronic Evaporative Humidification Cooling System www neptronic com Wiring Diagram...
Страница 18: ...18 Neptronic www neptronic com Evaporative Humidification Cooling System...
Страница 19: ...19 Neptronic Evaporative Humidification Cooling System www neptronic com...
Страница 20: ...20 Neptronic www neptronic com Evaporative Humidification Cooling System...
Страница 21: ...21 Neptronic Evaporative Humidification Cooling System www neptronic com...
Страница 22: ...22 Neptronic www neptronic com Evaporative Humidification Cooling System...
Страница 34: ...34 Neptronic www neptronic com Evaporative Humidification Cooling System...
Страница 35: ...35 Neptronic Evaporative Humidification Cooling System www neptronic com...
Страница 36: ...Neptronic 400 boul Lebeau Montreal Quebec H4N 1R6 CANADA TEL 514 333 1433 FAX 514 333 3163 www neptronic com...