Transients
Navigation: “Events” – “Definition” – “Transients”
Transients are stored in full sampling rate (sampling rate defined in
“Setup”-“Processing”).
A transient event can occur if specified conditions are met. As a condition a specific
quantity, their limits, hysteresis and type of hysteresis (level or time), phases and type of
window (inside limits or outside limits) can be defined.
The number of different quantities and the logical coupling between them (logical OR or
AND) can be selected.
If the value changes, the transient event is generated (edge trigger) and transients of
voltage and current are stored. Via window type (2) it can be selected if trigger should
start by entering the window with selected upper and lower limit or by leaving the window.
7
3
1
2
4
5
6
1.
Evaluated quantity
2.
Window type
3.
Limits
4.
Hysteresis type
5.
Hysteresis
6.
Phases
7.
Coupling between quantities
Storage Length and Pre-Trigger time of Transient can be defined in Misc. setup panel
(
Menu
Setup
Misc.
Transient
).