How to setup storing
Insert measurement name, description and place (2)
Set storing interval and multiplier (3,4). Interval can be selected from 200ms up to 2 hours
Select quantity groups that you want to store (5). Power Quality data storing and digital inputs
can be configured in separated tabs.
Select “Manually” or “By Time” condition to set up begin
and end of storing (6).
If there is the
“By Time” condition activated, select the
begin and end time of storing. (6). Clicking on Begin or End
time area opens that calendar dialog allowing choosing
begin and end time by selecting year, month, day, hour,
minute and second. A left click on hour, minute or second
area increases the value, while a right click decreases it.
Enable storing (1).
Select if changes will be applied to actual system only or to all systems (7)
supported only for multi-system instruments
Click Apply button to apply changes to instrument or Revert button to revert changes (8)
To stop storing, just Disable storing (1) and Apply changes (8).
Storing Options:
Harmonic U,I
Harmonics, THD, Interharmonics for voltage and current
Harmonic P,Q,S
Harmonic active, reactive and apparent power
Power
Active, apparent, reactive power, power factor, cos phi, etc.
Energy
positive, negative, total energy
Symmetrical Components
Zero, positive, negative sequence, unbalance factor
Analog Inputs
Additional analoge inputs
Harm.200Hz:
Storing of Supraharmonics (Higher Frequencies) in 200Hz bands up to 9kHz.
Harmonic 2kHz:
Storing of Supraharmonics in 2kHz bands up to 68kHz (500kHz for PQA8000H)
Half-Period RMS
This options stores for each defined storing interval (e.g. 200ms or 10min)
o
The maximal and minimal ½ period value for voltage and current
o
½ period current value at ½ period voltage MIN or MAX
o
½ period voltage at ½ period current MIN or MAX
This option might allow detecting the source of voltage events (load or generation)