STEP 1. Inspect shipping package and contents to ensure no damage has
occurred during shipping.
STEP 2. Remove both M6 flat head cap screws using a 4mm hex key and remove
sealed cap. If required angle is known, adjust luminaire angle by loosening two M8
socket head cap screws inside the slip fitter pole mount using a 6mm hex key.
After aiming torque M8 socket head cap screws to 17N-m (13ft-lb).
NOTE: Aiming angle can be adjusted after Step 6.
STEP 3.
Install slip fitter pole mount onto pole. Poles equivalent in size to 1-1/2" or 2" trade
size pipe or conduit are to be used. Ensure slip fitter pole mount is fully seated on
top of pole at the internal stops.
Aim and secure slip fitter pole mount using the six provided 3/8” hex bolts. Torque to
27N-m (20ft-lb)
NOTE: Aiming can be adjusted up to 180° in either direction after installation by loosening
the 6 hex bolts and tightening again to 27 N-m (20 ft-lb). DO NOT TURN BEYOND 180° as
this will induce twist and strain on conductors after wiring.
STEP 4.
Install a suitable wiring system that complies with the wiring methods permitted
in the Canadian Electrical Code or the National Electrical Code for the classification
of the hazardous locations area of installation.
STEP 5. Ensure wiring system has appropriate strain relief in the luminaire by tying a
large enough knot using the supply field wiring in the wiring compartment such that
it cannot be pulled through the 3/4" inch NPT entry of the luminaire.
STEP 6. Secure slip fitter pole mount to luminaire with four M6 hex head cap screws
provided using a 10mm socket. Torque to 7N-m (62in-lbs)
Step 7. Close sealed cap on slip fitter pole mount. Torque to 7N-m (62in-lbs)
Step 8. Follow the wiring instructions specified in the main installation instructions
provided with the AR luminaire as applicable for making connections with the luminaire
lead wires and testing the system.
15-16
www.nemalux.com | [email protected] | Tel 403•242•7475 | Fax 403•243•6190
MADE IN CANADA
TM
Nemalux
I N D U S T R I A L
AR Series
rev. A-30
WARNING / ATTENTION
INSTALLATION STEPS
AR-SFY – SLIP FITTER YOKE MOUNT
(Ordered Separately)
This AR-SFY kit is intended for use with UL Listed
AR luminaire as marked on the luminaire nameplate.
Accessory Package Contents
AR-SFY
PART NAME
QTY
2
1
2
6
4
1
M6 X 16mm FLAT HEX HEAD SOCKET CAP SCREW
SEALED CAP
M8 X 25mm SOCKET HEAD CAP SCREWS
3/8” HEX BOLTS
M6 X 16mm HEX HEAD CAP SCREW
SLIP FITTER YOKE MOUNT (2x PIECES)
M8 ADJUSTMENT SCREWS
Listing for Class II, Division 2, Zone
22, Class III, Nonrecessed Marine
Luminaire and the IP66 or IP66/67
rating are Limited to using the
mount for mechanical support only
and not part of the wiring system.
BORE SIZED FOR 2"
TRADE SIZE POLE
53-63mm (2 1-8" TO
2 7-16") DIAMETER
6 X SET SCREW
B
B
INNER STEP BORE SIZED FOR 1.5" TRADE SIZE POLE
46mm - 50mm (1 13-16" TO 2")
SECTION B-B
BOTTOM OUT STEP FOR
TRADE SIZE 1.5" POLE
BOTTOM OUT STEP FOR
TRADE SIZE 2" POLE
Warning: Listing for Class II, Division 2,
Zone 22, Class III, Nonrecessed Marine
Luminaire and the IP66 or IP66/67 rating
are Limited to using the mount for
mechanical support only (¾” NPT Conduit
entry covered by mount is to be plugged
using provided plugs) and not part of the
wiring system.
Luminaires marins de classe II, division 2, zone 22,
classe III, non-encastré et la classification IP66 ou
IP66/67 sont limitées à l'utilisation du support
pour un support mécanique uniquement (l'entrée
de conduit ¾” NPT couverte par le support doit
être branchée à l'aide des bouchons fournies).
Il n'est pas autorisé à être utilisé pour le système
de câblage.
Luminaires marins de classe II, division 2,
zone 22, classe III, non-encastré et la
classification IP66 ou IP66 / 67 sont
limitées à l'utilisation du support pour un
support mécanique uniquement (l'entrée
de conduit ¾” NPT couverte par le
support doit être branchée à l'aide des
bouchons fournies). Il n'est pas autorisé à
être utilisé pour le système de câblage.
WARNING:
The AR Head must not face
upwards by any degree
beyond the vertical position
for Class II, Division 2,
Zone 22, and Class III
hazardous locations.
LIGHT BEAM
HORIZON
ATTENTION:
Le luminaire (AR) ne doit pas
être orientée vers le haut de
quelque degré que ce soit
au-delà de la position verticale
pour les emplacements
dangereux de Classe II,
Division 2, Zone 22 et Classe III