4.2.51 Fire Alarm input Setting
Parameter “Fire_Al_Set “ sets the digital input DI10, to be sensitive to a high or low input signal.
The input activates by either Low signal, e.g. “Fire Alarm” or by a High signal “RPS Rapture Panel Sensor”
Se electrical schematics for more information on how to connect to sensor input.
ESC
OK
MFdP Se!.
1/2
dPSS =50
dPSR =50
dPDS =50
dPDR =50
MFPP =30
Switch = On = Alarm when digital input10 = High (24V)
Switch = Off =Alarm when digital input10 = Low (0V)
5 Automatic bin emptying function
5.1 AEB-Flap Valve settings
5.1.1 Hardware
• The AEB-Flap Valve controlled by the V11 TVFD (SLV) Solenoid Lower Valve.
• The duct isolation valve controlled by the V12 TVFD (SUV) Solenoid Upper Valve.
5.1.2 PLC Settings
1 Presep Switch = Off (standard setting).
2 AEB-TVFD Switch = On (standard setting).
3 TVFDAdv Switch = Off (standard setting).
Presep overrides 2 above.
If TVFDAdv is activated (Switch = On), TVFDAdv overrides 1 and 2 above.
5.1.3 Timer Settings
BinOpnTm
TL = Delay time to let the motor decrease speed and the TVFD Solenoid Upper Valve to close a duct isolation
valve before bin emptying starts. The default is 5 seconds.
TH = Emptying Time. The default is 5 seconds.
PresepTm
TL = Delay to let the bin lid close before the motor increases speed and the TVFD Solenoid Upper Valve to open
a duct isolation valve. The default is 5 seconds.
TH = Time delay to the next possible emptying sequence. The default is 5 seconds.