FlexPAK
4.2.13 BLI-Wr
Menu for setting the delay time for the Bin Level Indicator warning message. When the BLI signal disappears,
the BLI-Wr timer is activated. When the timer elapses, the message ‘Warning! Dustbin Full’ is activated, see
.
ESC
OK
BLI-Wr
1/1
T
= 12:00m
Ta = 00:00m
T=12:00m: Time before message “Warning! Dustbin Full’ is activated. The
default is 12 minutes.
Ta=00:00: Elapsed time since the BLI-sensor was activated.
4.2.14 AEBTme
Menu for Automatic Emptying of the collector Bin, interval Timer settings. This function is only available when
. When AEBTme elapses, it activates the dust bin emptying
sequence with either the AEB - Flap Valve, simple TVFD, Advance TVFD or pre-separator.
ESC
OK
BLI-Wr
1/1
T
= 12:00m
Ta = 00:00m
TH=01:00s: Do not change the default setting of 1 second.
TL=60:00m: The amount of time between emptying cycles. The default
setting is 60 minutes.
Ta=00:00: The elapsed time since the last AEB was activated.
4.2.15 BinOpnTm
Menu for AEB-Flap Valve, simple TVFD and pre-separator opening cycle settings. The values for ‘TL’ and ‘TH’ de-
pend on which function is being used. See
ESC
OK
BinOpnTm
1/1
TH = 05:00s
TL = 03:00s
Ta = 00:00s
TL= See
4.2.16 CFDPS-Al
Menu for setting the delay time for the Control Filter DP Sensor Alarm (CFDPS-Al). When the Control Filter pres-
sure sensor monitoring detect High dP across Control Filter, the CFDPS-Al timer is activated. When this timer has
elapsed, the unit goes into Off mode and an alarm is displayed in the PLC. See
Section 3.3.8 Alarm! Control Filter
.
ESC
OK
CFDPS-Al
1/1
T
= 5:00s
Ta = 00:00s
T=05:00s: Time before CFDPS-Al is activated. The default setting is 5
seconds.
Ta=00:00: The elapsed time since High dP across Control Filter was detec-
ted.
32