3.1.15 Pressure Sensor Display
The Pressure Sensor Reading display is manually activated.
ESC
OK
Thu
10:45
2018-02-01
ESC
OK
ESC + C 9/9
Date Window
Arrow Window
The display is activated by the following sequence:
• Toggle with arrow key “UP” or “Down” until Date Window is visible.
• Toggle with arrow key “Left” or “Right” until Arrow Window is visible.
Press the “ESC” button simultaneously while pressing the arrow key “Up” to view pressure sensor data. Pressure
sensor data is only available if a pressure sensor is physically installed and sensor setup is done in the parameter
setting.
• CFdP Setting “Stat = ON” (Control Filter Sensor)
• MFdP Setting “Stat = ON” (Main Filter Sensor)
• Stat = On
→
Activated sensor input for Analog sensor 0-10V
• Stat = Off
→
Activated sensor input for Dp Switch input configuration
Displayed when only Main Filter is installed
ESC
OK
Ppump -20 kPa
Total System
Pressure Dropp
SystdP 3.1 kPa
Duct P 16.9 kPa
MaxdP 5.0 kPa
ESC
MFdP Setting, Set = ON
CFdP Setting, Set = OFF
Press “OK” button to close display.
Ppump
-20 kPa
→
Pressure readings from the pump pressure sensor
SystdP
3.1 kPA
→
dp pressure System “dp Pump to the dirty side of filter”
Duct P
-16.9 kPa
→
Pressure sensor readings from a sensor placed on filter dirty side or
duct
MaxdP
5.0 kPa
→
Main Filter Max dp pressure Limit setting
See “CFdP Setting” for more information
Displayed when only Control Filter is installed
ESC
OK
Ppump -21 kPa
CF dP 2.8 kPa
Max dP 5.0 kPa
ESC
MFdP Setting, Set = OFF
CFdP Setting, Set = ON
Press the “OK” button to close the display.