3.3.14 Alarm! Dustbin Full
When a level indicator set for a time delay of 30 minutes is activated, then when the delay has elapsed a mes-
sage “Alarm! Dustbin Full” appears on the display and the unit is stopped.
Empty the dust bin and press the OK button to reset the Alarm.
ESC
OK
Alarm!
Dustbin Full
Max Time lapsed
Mo 09:50
Unit is Stopped
Reset OK ==>
3.3.15 Alarm! Main Filter Clogged
When the Delta pressure indicator is set, the MFDPS-Al timer starts to count down. When the set time has
elapsed (T = 30.00 m), then the message, “Alarm Main Filter Clogged” appears on the display and the Start/Stop
button starts to flash. The unit is stopped. Fix the problem with the clogged filter.
Press the OK button to reset the Alarm.
ESC
OK
Alarm!
Main
Filter Clogged
Th 12:23
Unit is Stopped
Reset OK-->
3.3.16 AUX Hi Temp Limit Exceeded
This message is displayed when AUX temperature exceeds the “Max Set” temperature limit-setting and stop
delay timer is elapsed. See AUX Setting.
When the AUX temperature is below the “Max Reset “temperature limit. Press the green OK button to reset the
alarm.
Temp
51 C
→
Shows the actual temperature value
MaxSet
50 C
→
Shows Max Set Temperature limit setting
MinReset
50 C
→
Shows Max Reset Temperature limit setting
TimeToUnitStop
31:00
→
Shows the remaining time until the unit stops
Default settings Max Set = Max Reset = 50 C