FlexPAK
3.3.4 Low Pressure or Duct Isolation Released
The Compressed Air Switch (CAS) indicates that the compressed air pressure is too low.
Or, there is a duct isolation valve connected to the system that has released and isolated FlexPAK from the duct
system. Check the isolation valve release sensor, released isolation valve = open electrical circuit to input on
PLC.
Press the green OK button to reset the alarm.
ESC
OK
Low Pressure
CAS<3Bar Or
Duct Isolation
Valve
Released
Th 11:23
Reset OK ==>
3.3.5 Alarm! Hi Vacuum
The maximum vacuum level has been activated, and the delay time for the vacuum alarm has elapsed. Press OK
to reset the alarm.
ESC
OK
Alarm!
Hi Vacuum
Level > -36 kPA
Th 12:23
Unit is Stopped
Reset OK==>
3.3.6 Exhaust Air Temp High
The temperature of the air exiting the pump has exceeded the maximum allowable limit of 135ºC (275ºF). When
the ‘Current Value’ has become lower than 90°C (194ºF), press OK to reset the alarm. Check for the cooling air
valve or PT100 sensor values.
ESC
OK
Max Temp Exhaust
Air Exceeded
Unit is Stopped
Limit 135 °C
Current 130 °C
Reset OK
à
3.3.7 Bag Replacement Switch Time Out
The maximum amount of time for the bag replacement being ‘On’ has been exceeded. To restart the unit, the
alarm needs to be reset by turning the bag replacement switch (SC2) to ‘Off‘ and pressing the OK button to reset
.
ESC
OK
Bag Replacment
Switch Time Out
Th11:23
Unit is Stopped
Reset OK ==>
20
Содержание FlexPAK
Страница 7: ...FlexPAK 2 7 ...
Страница 54: ...FlexPAK PLC setting Default value Customer specific value 54 ...
Страница 55: ...www nederman com ...