Breaker Racking Position Rocker Arm
As the Citadel breaker racks into the connect position - the front of the breaker racking
position rocker arm seesaws upwards.
As it does - it moves the breaker position indicator actuator on the inside of the
switchgear front door which move the semaphore indicator on the front of the
switchgear door indicating the breakers postions (disconnect / connect).
Optionally - the dogleg in the racking arm can engage a latch on the inside of the front
door to insure that no one can open the switchgear door if the breaker is racked into the
connect position.
This feature comes disabled. It can be enabled by desirous customers.
NOTE; the switchgear door CANNOT be open unless breaker is tripped open and
racked into the disconnect positon through the closed switchgear door.
Any attempt to open the door with the breaker in any position OTHER than fully
Dis-Connected, WILL damage parts if force is exerted.
This condition will NEVER be considered a warranty claim and WILL do material
damage and possible personal injury if attempted.
Breaker racking
position rocker arm
FIGURE 36
S W I T C H G E A R C U B I C L E & D R A W - O U T F E A T U R E S