Since the closing spring is automatically recharged by the motor operating
mechanism when the breaker has closed; the operating mechanism is capable of an
open-close-open duty cycle as required for rapid auto-reclosing.
Opening
The tripping spring is charged during closing. To open the breaker, press the trip
button until the vacuum breaker has tripped and “OPEN” is displayed by indicator.
Manual Operation
Electrically operated vacuum breakers can be operated manually if the control
supply should fail.
Manually Charging the Closing Spring
Insert the hand-crank in hole and turn clockwise until charge spring
mechanism “clicks” and indicator shows spring “CHARGED”.
FIGURE: 3
Open Operation
Close Operation
Manual
Charging
Tool
Insert Point
for Manual
Charging Tool
Open | Close
indicator
Spring-condition
indicator
I N I T I A L C H E C K S A N D F U N C T I O N A L T E S T I N G