Citadel 2.0 - Instruction Manual - page:
49
IM
-
C
2.0
-
12
/2
5
/3
0/
4
0/
DO
/F
X
| V
: 1
0 / 1
1 / 2
0
21
Micro-switch S28 - cuts motor circuit during racking procedure.
OFF
OFF
ON
ON
FIGURE 23
If Citadel breaker control component concerns exist;
Micro-Switch Checks should include:
• No breakage or excessive wear of the plastic housing.
• Proper alignment of the switch plunger.
• Proper throw of the device pushing & releasing the plunger.
• Electrical integrity of the wiring connections to the micro-switch.
• Integrity of the switches operation by using an ohmmeter across switch output terminals
with at least one of the leads removed.
Push plunger & insure switch opens and closes properly with virtually no electrical resistance in the
closed position. Verify switch is changing contact state correctly as per the movement of its driving
actuator pin.
C I T A D E L C O N T R O L S