Citadel 2.0 - Instruction Manual - page:
149
IM
-
C
2.0
-
12
/2
5
/3
0/
4
0/
DO
/F
X
| V
: 1
0 / 1
1 / 2
0
21
Symptom
Cause
Action
Breaker will not charge
Motor switch off
Check Cable of Motor Line
No control power
Breaker in Disconnect Position
Motor will not run
Replace the Motor
Spring charged
Check the Spring Charged Indicator
Breaker will not close
Closing spring not charged
Charge Closing Spring
Breaker closed
Check the Position Indicator
Breaker is not in proper
position
Set into the Disconnect, Test, or
Connect Position
No electrical close signal
Verify Control Power Available Check
Close Solenoid
Breaker will not open
Breaker open
Check the Position Indicator
No electrical open signal
Verify Control Power Available
Check the Open Solenoid
TABLE 20 - TROUBLESHOOTING GUIDE