Citadel 2.0 - Instruction Manual - page:
45
IM
-
C
2.0
-
12
/2
5
/3
0/
4
0/
DO
/F
X
| V
: 1
0 / 1
1 / 2
0
21
ANSI/IEEE C37.06
control voltages
Close coil
Trip coil
Coil
resistance in
ohm’s
Nominal
Range
5
Close
Trip
A
1
A
1
24 Vdc
19-28
14-28
Consult Factory
2.5
48 Vdc
36-56
28-56
6.5
11.0 / 20.0
3
8.0
125 Vdc
6
90-140
70-140
2.1
3.2 / 6.0
3
43.0
250 Vdc
180-280
140-280
1.2
1.9 / 3.5
3
158.0
120 Vac
104-127
---
4
2.4
---
2,4
43.0
240 Vac
208-254
---
4
1.3
---
2,4
158.0
Footnotes:
(1) Current at nominal voltage
(2) Capacitor trip
(3) Value preceding slash (/) is the current for the standard trip coil with
standard rating interrupting time. Value following (/) is current for
optional trip coil with three-cycle interrupting time.
(4) ---- means this selection is not available at this voltage.
(5) ---- consult factory for special extended ranges.
(6) 90V is standard for The Citadel
TABLE 10
C I T A D E L C O N T R O L S
Motor Lead
Second
Trip coil
Close & Trip
Coil
FIGURE 20