Breaker Open - Close indication actuator for front door indication
The Citadel can uniquely let personnel know the breaker is open or closed – even if the
switchgear front door is shut.
On the right side of the breaker is a cam actuator that rotates as the breaker opens and
closes. (Feature #13, page 56)
The cam presses down on the actuator mechanism located on the right side of the
switchgear cell wall.
As the cam forces the actuator down – the actuator slides the bracket on the inside of the
cell door which in turn moves the front door indication semaphore.
Cam rotates forcing
actuator down
FIGURE 39A
FIGURE 40
FIGURE 39B
FIGURE 41
S W I T C H G E A R C U B I C L E & D R A W - O U T F E A T U R E S