B-MOC
(Patent pending)
When Customers wish to increase the number of auxiliary contacts – the rugged
mounting frames for holding the moving & stationary secondary contact block
assemblies can be fitted with an addition set of secondary male and female contact
block(s). This assembly is known as a B-MOC (Better Mechanism Operated Control)
switch assembly. The B-MOC will provide additional normally “a” and normally “b” and
form-C contacts. The contacts all follow the operation of the breaker (either identically
or in opposition) and are wired to the breaker’s internal auxiliary control switch.
Factory wiring uses 14 gauge SIS wire. The circuits are conservatively rated at a
maximum of 250 V AC/DC and 10 amps.
See Control Wiring diagrams for the pin out functions associated with each wiring point.
Contact the factory to optionally obtain extended voltage and current ranges on control