123
Appendixes
WARNING
Fire and Explosion Hazard
To prevent serious injury or death:
●
DO NOT adjust or attempt to measure gas
valve outlet pressure. The gas valve is factory-
set for the correct outlet pressure. This setting
is suitable for natural gas and propane,
requiring no field adjustment.
●
Attempting to alter or measure the gas valve
outlet pressure could result in damage to
the valve, causing potential severe personal
injury, death or substantial property damage.
Navien NHB-H boilers are shipped ready to
fire natural gas ONLY.
O-ring
Gasket
Gas Orifice
O-ring
Figure 5. Exploded View of Gas Pipe Assembly
DANGER
Fire and Explosion Hazard
To prevent serious injury or death:
●
ALWAYS inspect the O-ring between the gas
valve and gas valve inlet adapter whenever
they are disassembled (see Figure 5).
●
The O-ring must be in good condition and
must be installed. Replace O-ring if needed.
GAS : NG
NAC-NH150
4.70 / 6.60
GAS : LP
NAC-L150
3.65 / 5.05
Figure 6. Orifice Identification
10. Once the gas inlet pipe is detached from the gas
valve, find location B - the connection above the
gas valve where it is attached to the fan motor
assembly. Carefully remove the four screws by
hand using a Phillips screwdriver and pull the
gas valve away from the fan assembly to access
the gas orifice.
Location
B: Remove
4 screws here
Location
A: Remove
2 screws here
Figure 3. Detaching Gas Valve from
Gas Inlet Pipe and Fan Motor Assembly
11. Once the Gas Orifice is exposed, remove the
two screws that hold the part in place. Remove
the Gas Orifice from its housing and prepare
the new Gas Orifice for the LP conversion for
installation.
Remove two
2 screws
here
Figure 4. Access to Gas Orifice in Fan Assembly
Содержание NHB H Series
Страница 137: ...137 Appendixes 12 6 3 Fan Gas Assembly 3 1 5 4 16 5 14 7 6 13 20 19 18 12 17 8 11 10 9 15 21 2...
Страница 142: ......