123
Appendixes
12.1 Gas & High Altitude
Conversion
This boiler is configured for Natural Gas at the factory.
●
If conversion to Propane Gas is required by the boiler,
use the LP CONVERSION KIT supplied with the boiler.
●
If the boiler is installed at a high altitude
(above 5,400 ft) for NG, use the HIGH ALTITUDE
CONVERSION KIT supplied with the boiler.
Note
●
For NG high altitude conversion, use
the HIGH ALTITUDE CONVERSION KIT.
●
For LP high altitude conversion, use
the LP CONVERSION KIT. Note that the
Gas Orifice from the LP CONVERSION
KIT covers the boiler’s installation at an
altitude of 0 to 10,100 ft.
DANGER
Do not perform a gas & High Altitude conversion
without an officially approved conversion kit and
the instructions supplied by Navien. Gas & High
Altitude conversion using any other parts will result
in extremely dangerous burner operation, leading
to fire, explosion, severe personal injury or death.
Note
High Altitude Conversion kit (a) and
Propane Conversion kit (b) are attached
to the inside of Product’s case.
High Altitude
Conversion Kit (a)
and Propane
Conversion Kit (b)
a.
High Altitude Conversion Kit
b.
Propane Conversion Kit
WARNING
●
This conversion kit must be installed by a
qualified service agency* in accordance
with Navien’s instructions and all applicable
codes and requirements of the authority
having jurisdiction. The information in these
instructions must be followed to minimize
the risk of fire or explosion or to prevent
property damage, personal injury or death.
The qualified service agency is responsible
for the proper installation of this kit. The
installation is not proper and complete until
the operation of the converted appliance is
checked as specified in the manufacturer’s
instructions supplied with the kit.
●
Turn off electrical supply to the boiler and
close the manual gas shut-off valve to isolate
the boiler during conversion. Allow the boiler
to cool if it has been operating.
●
For propane boilers: The propane supplier
mixes an odorant with the propane to make
its presence detectable. In some instances the
odorant can fade, and the gas may no longer
have an odor. Before startup (and periodically
thereafter), have the propane supplier verify
the correct odorant level in the gas.
* A qualified service agency is any individual, firm,
corporation or company which either in person or
through a representative is engaged in and is responsible
for the connection, utilization, repair or servicing of gas
utilization equipment or accessories; who is experienced
in such work, familiar with all precautions required,
and has complied with all of the requirements of the
authority having jurisdiction.
In Canada
: The conversion shall be carried out in
accordance with the requirements of the provincial
authorities having jurisdiction and in accordance
with the requirements of the CAN‐B149.1 and CAN1‐
B149.2 Installation Code.
12. Appendixes
Содержание NCB-190/060H
Страница 137: ...137 Appendixes 12 6 2 Burner Assembly 12 13 10 20 21 11 7 3 1 2 5 24 6 9 23 22 8 14 19 16 17 10 15 18 4...
Страница 141: ...141 Appendixes 12 6 4 Fan Gas Assembly 10 9 12 8 7 3 1 2 4 5 6 13 11 11 14 15...
Страница 143: ...Memo...
Страница 144: ......