122 Operating the Boiler
Error Code Reason
Self-Diagnostic/ Action
E434
Abnormal operation: water adjustment
valve
Contact technical support at 1-800-519-8794.
E439
Abnormal operation: flow sensor
Contact technical support at 1-800-519-8794.
E441
Domestic hot 2: thermistor open or short
circuit
Contact technical support at 1-800-519-8794.
E445
Abnormal operation: Bypass mixing valve
Contact technical support at 1-800-519-8794.
E515
Abnormal operation: PCB
●
Ensure that the electrical cord is properly
grounded.
●
Reset the boiler from the front panel.
E517
Abnormal operation: Dip switch setting
Contact technical support at 1-800-519-8794.
E594
Abnormal operation: EEPROM
Contact technical support at 1-800-519-8794.
E615
Abnormal operation: input and memory
Contact technical support at 1-800-519-8794.
E736
Abnormal operation: cascade
communication
Contact technical support at 1-800-519-8794.
E740
Abnormal operation: outdoor temperature
sensor (appears only when the outdoor
reset curve is enabled).
●
Ensure that the outdoor reset curve is configured
properly.
●
Check the outdoor temperature sensor wiring
connection.
E761
Abnormal operation: Pre-Heat Aquastat
●
Check the Pre-Heat Aquastat wiring connection.
●
Select an option other than Aquastat mode.
E762
Abnormal flue gas duct: Vent pipe not
properly inserted
Contact technical support at 1-800-519-8794.
E773
Using the wrong gas
Contact technical support at 1-800-519-8794.
E777
LWCO (service code: 7700) (external device)
●
Check the LWCO wiring connection.
●
Ensure that the system water level is appropriate.
●
Add make-up water to the system if necessary.
E782
Abnormal operation: main panel
communication
Contact technical support at 1-800-519-8794.
E784
Abnormal operation: zone controller
communication
Contact technical support at 1-800-519-8794.
E786
Improper front panel
Contact technical support at 1-800-519-8794.
E788
Abnormal Gas Setting
Check the supplied gas type and match the gas type
setting on the PCB DIP switch.
If any of these remedies do not resolve the problem, contact Technical Support at 1-800-519-8794.
Содержание NCB-190/060H
Страница 137: ...137 Appendixes 12 6 2 Burner Assembly 12 13 10 20 21 11 7 3 1 2 5 24 6 9 23 22 8 14 19 16 17 10 15 18 4...
Страница 141: ...141 Appendixes 12 6 4 Fan Gas Assembly 10 9 12 8 7 3 1 2 4 5 6 13 11 11 14 15...
Страница 143: ...Memo...