53
Chassis (Cooling Section)
Thermal Expansion Valve (TXV)
The TXV is located underneath the control deck. The TXV meters refrigerant based on pressures
in the system and temperatures at the bulb location. The spring tension plus the evaporator
pressure (which is measured through the external equalizer tube) counter the pressure in the
power element. As the bulb becomes warmer it increases the pressure in the diaphragm of the
power element which opens the valve. The valve closes as the evaporator pressure increases
and/or the bulb temperature decreases.
Example – The bulb temperature at the outlet of the evaporator is 55°F which equals 155 psig
of diaphragm pressure. The evaporator pressure taken from the external equalizer line at the
outlet of the evaporator is 110 psig. This added to the spring tension of 25 psig equals a total
of 135 psig. The 155 psig diaphragm pressure is greater than the 135 psig combined spring
and evaporator pressure so the valve will begin feeding refrigerant
The TXV Bulb (attached to the power element) must be securely fastened and firmly insulated
to the suction line as shown below.
If you are experiencing system pump down, inspect the external equalizer tubing for restriction.
BULB SECURED
TIGHTLY TO
SUCTION LINE
BULB INSULATED
FIRMLY
IDEAL LOCATION
FOR CHECKING SUPER HEAT
Distributor
TXV LOCATED UNDER
CONTROL DECK
14
27
51
23
THERMAL EXPANSION
VALVE (TXV)
Содержание CPG41838-U
Страница 2: ...2...
Страница 5: ...5 Unit Dimensions Original R22 with Gas Heat A B Series 43...
Страница 6: ...6 Original R22 with Electric Heat A B Series Unit Dimensions...
Страница 7: ...7 Unit Dimensions Original R410A with Gas Heat B C D E Series...
Страница 8: ...8 Unit Dimensions Original R410A with Electric Heat B C D E Series...
Страница 9: ...9 Unit Dimensions U Series R410A 80 Gas Heat...
Страница 10: ...10 Unit Dimensions U Series R410A up to 95 Gas Heat...
Страница 11: ...11 Unit Dimensions U Series R410A Electric Heat...
Страница 19: ...19 Gas Furnace 3 Remove the 11 screws 4 Remove the front furnace baffle...
Страница 46: ...46 Chassis Cooling Section...
Страница 79: ...79...