![National Comfort Products CPG41838-U Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/national-comfort-products/cpg41838-u/cpg41838-u_instruction-manual_3358708052.webp)
Chassis (Cooling Section)
After verifying the wiring, document the following information and compare to the specification
on the compressor's data tag.
• Incoming voltage to compressor at contactor
• Compressor starting amps
• Ohm reading between C&S on compressor terminals
• Ohm reading between C&R on compressor terminals
• Ohm reading between R&S on compressor terminals
• Ohm reading between each compressor terminal and ground
Verify the run capacitor charge in microfarads by measuring between HERM
and COM terminals.
Do the same for the start capacitor if used.
When diagnosing a compressor that is operating, document the following:
• Suction Pressure
• Discharge Pressure
• Suction Temperature
• Discharge Temperature
• Super Heat
• Subcooling
VERIFY 24 VOLTS TO THE
CONTACTOR COIL
VERIFY THAT THE POWER
WIRE TO THE COMMON (C) ON
THE CAPACITOR COMES FROM
THE SAME POINT ON THE
CONTACTOR THAT THE WIRE
GOING TO THE RUN WINDING
(R) ON THE COMPRESSOR IS
VERIFY 240 VOLTS LEAVING
THE CONTACTOR
HERM
FAN
TOP VIEW OF CAPACITOR
C
52
Содержание CPG41838-U
Страница 2: ...2...
Страница 5: ...5 Unit Dimensions Original R22 with Gas Heat A B Series 43...
Страница 6: ...6 Original R22 with Electric Heat A B Series Unit Dimensions...
Страница 7: ...7 Unit Dimensions Original R410A with Gas Heat B C D E Series...
Страница 8: ...8 Unit Dimensions Original R410A with Electric Heat B C D E Series...
Страница 9: ...9 Unit Dimensions U Series R410A 80 Gas Heat...
Страница 10: ...10 Unit Dimensions U Series R410A up to 95 Gas Heat...
Страница 11: ...11 Unit Dimensions U Series R410A Electric Heat...
Страница 19: ...19 Gas Furnace 3 Remove the 11 screws 4 Remove the front furnace baffle...
Страница 46: ...46 Chassis Cooling Section...
Страница 79: ...79...