41
Electric Furnace
CPE Control Board
Faults – If multiple inputs are received with a cooling input (Y)
then the board will automatically fault and run in cooling.
Cooling Blower Operation – Cooling fan will delay 5 seconds on
a call for cooling and will delay off when a call is terminated for
the duration of the board jumper set point.
(A = 5 sec., B = 30 sec., C = 60 sec., D = 90 sec.)
High Limit Switch
The high limit switch protects the strip heaters from overheating due to lack of indoor airflow.
This switch breaks a line voltage directly to the heat elements.
The high limit switch is located on the left side of the electric strip heaters.
The high limit switch is normally closed, opens at 175°F +/- 5°F with an automatic reset
differential of 40°F and is wired in series with the heater element.
To prove the high limit switch has failed open, use an ohmmeter and verify there is no
continuity across the terminals once the limit has cooled below the differential setting.
If the unit is experiencing high limit failures or constant tripping, verify your temperature rise
(see page 22) and check for the following:
Restricted airflow
• Blocked or dirty air filter
• Blocked or dirty return air grille
• Blocked supply duct (closed fire dampers)
• Blower motor not running (weak capacitor, low voltage)
In order to calculate CFM use the formula:
CFM = Voltage x Amperage x 3.414 / (1.08 x
Δ
T)
Size
3 kW
5 kW
7 kW
10 kW
15 kW
Banks
2
2
2
2
3
Ohms per bank (Ω)
30.4
20.8
14.81
10.4
10.4
Содержание CPG41838-U
Страница 2: ...2...
Страница 5: ...5 Unit Dimensions Original R22 with Gas Heat A B Series 43...
Страница 6: ...6 Original R22 with Electric Heat A B Series Unit Dimensions...
Страница 7: ...7 Unit Dimensions Original R410A with Gas Heat B C D E Series...
Страница 8: ...8 Unit Dimensions Original R410A with Electric Heat B C D E Series...
Страница 9: ...9 Unit Dimensions U Series R410A 80 Gas Heat...
Страница 10: ...10 Unit Dimensions U Series R410A up to 95 Gas Heat...
Страница 11: ...11 Unit Dimensions U Series R410A Electric Heat...
Страница 19: ...19 Gas Furnace 3 Remove the 11 screws 4 Remove the front furnace baffle...
Страница 46: ...46 Chassis Cooling Section...
Страница 79: ...79...